550 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 15.29V (2.21%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 50.44V (7.31%)
Voltage at Load674.7 VLine Loss: 14565.4 W
Max Power & Breaker657.31 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8154.5 V (1181.81%)0.0 V13451.11 V (1949.44%)7768200.0 WDrop High
2.5 mm²24 A18 A4892.7 V (709.09%)0.0 V8070.66 V (1169.66%)4660920.0 WDrop High
4 mm²32 A25 A3057.94 V (443.18%)0.0 V5044.16 V (731.04%)2913075.0 WDrop High
6 mm²41 A32 A2038.62 V (295.45%)0.0 V3362.78 V (487.36%)1942050.0 WDrop High
10 mm²57 A44 A1223.17 V (177.27%)0.0 V2017.67 V (292.42%)1165230.0 WDrop High
16 mm²76 A59 A764.48 V (110.79%)0.0 V1261.04 V (182.76%)728268.8 WDrop High
25 mm²101 A78 A489.27 V (70.91%)200.7 V807.07 V (116.97%)466092.0 WDrop High
35 mm²125 A97 A349.48 V (50.65%)340.5 V576.48 V (83.55%)332922.9 WDrop High
50 mm²151 A118 A244.63 V (35.45%)445.4 V403.53 V (58.48%)233046.0 WDrop High
70 mm²192 A150 A174.74 V (25.32%)515.3 V288.24 V (41.77%)166461.4 WDrop High
95 mm²232 A181 A128.76 V (18.66%)561.2 V212.39 V (30.78%)122655.8 WDrop High
120 mm²269 A210 A101.93 V (14.77%)588.1 V168.14 V (24.37%)97102.5 WDrop High
150 mm²309 A241 A81.54 V (11.82%)608.5 V134.51 V (19.49%)77682.0 WDrop High
185 mm²353 A275 A66.12 V (9.58%)623.9 V109.06 V (15.81%)62985.4 WDrop High
240 mm²415 A324 A50.97 V (7.39%)639.0 V84.07 V (12.18%)48551.2 WDrop High
300 mm²477 A372 A40.77 V (5.91%)649.2 V67.26 V (9.75%)38841.0 WDrop High
400 mm²570 A445 A30.58 V (4.43%)659.4 V50.44 V (7.31%)29130.7 W~ ≤5%

FAQ — 550 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 550A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 550A over 600m at 690V (voltage drop: 15.29V or 2.21%).

What is the power capacity of 550A at 690V?

At unity power factor, 550A at 690V supports 657.31 kW with a standard 600A circuit breaker.