700 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.89V (0.94%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.84V (3.09%)
Voltage at Load411.1 VLine Loss: 4718.7 W
Max Power & Breaker503.16 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2075.69 V (500.17%)0.0 V3423.92 V (825.04%)2516640.0 WDrop High
2.5 mm²24 A18 A1245.41 V (300.1%)0.0 V2054.35 V (495.02%)1509984.0 WDrop High
4 mm²32 A25 A778.38 V (187.56%)0.0 V1283.97 V (309.39%)943740.0 WDrop High
6 mm²41 A32 A518.92 V (125.04%)0.0 V855.98 V (206.26%)629160.0 WDrop High
10 mm²57 A44 A311.35 V (75.02%)103.6 V513.59 V (123.76%)377496.0 WDrop High
16 mm²76 A59 A194.6 V (46.89%)220.4 V320.99 V (77.35%)235935.0 WDrop High
25 mm²101 A78 A124.54 V (30.01%)290.5 V205.44 V (49.5%)150998.4 WDrop High
35 mm²125 A97 A88.96 V (21.44%)326.0 V146.74 V (35.36%)107856.0 WDrop High
50 mm²151 A118 A62.27 V (15.0%)352.7 V102.72 V (24.75%)75499.2 WDrop High
70 mm²192 A150 A44.48 V (10.72%)370.5 V73.37 V (17.68%)53928.0 WDrop High
95 mm²232 A181 A32.77 V (7.9%)382.2 V54.06 V (13.03%)39736.4 WDrop High
120 mm²269 A210 A25.95 V (6.25%)389.1 V42.8 V (10.31%)31458.0 WDrop High
150 mm²309 A241 A20.76 V (5.0%)394.2 V34.24 V (8.25%)25166.4 WDrop High
185 mm²353 A275 A16.83 V (4.06%)398.2 V27.76 V (6.69%)20405.2 WDrop High
240 mm²415 A324 A12.97 V (3.13%)402.0 V21.4 V (5.16%)15729.0 WDrop High
300 mm²477 A372 A10.38 V (2.5%)404.6 V17.12 V (4.13%)12583.2 WDrop High
400 mm²570 A445 A7.78 V (1.88%)407.2 V12.84 V (3.09%)9437.4 WDrop High

FAQ — 700 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 700A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 120m at 415V (voltage drop: 3.89V or 0.94%).

What is the power capacity of 700A at 415V?

At unity power factor, 700A at 415V supports 503.16 kW with a standard 700A circuit breaker.