700 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.11V (1.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 26.75V (6.45%)
Voltage at Load406.9 VLine Loss: 9830.6 W
Max Power & Breaker503.16 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4324.35 V (1042.01%)0.0 V7133.16 V (1718.83%)5243000.0 WDrop High
2.5 mm²24 A18 A2594.61 V (625.21%)0.0 V4279.9 V (1031.3%)3145800.0 WDrop High
4 mm²32 A25 A1621.63 V (390.75%)0.0 V2674.94 V (644.56%)1966125.0 WDrop High
6 mm²41 A32 A1081.09 V (260.5%)0.0 V1783.29 V (429.71%)1310750.0 WDrop High
10 mm²57 A44 A648.65 V (156.3%)0.0 V1069.97 V (257.83%)786450.0 WDrop High
16 mm²76 A59 A405.41 V (97.69%)9.6 V668.73 V (161.14%)491531.2 WDrop High
25 mm²101 A78 A259.46 V (62.52%)155.5 V427.99 V (103.13%)314580.0 WDrop High
35 mm²125 A97 A185.33 V (44.66%)229.7 V305.71 V (73.66%)224700.0 WDrop High
50 mm²151 A118 A129.73 V (31.26%)285.3 V213.99 V (51.57%)157290.0 WDrop High
70 mm²192 A150 A92.66 V (22.33%)322.3 V152.85 V (36.83%)112350.0 WDrop High
95 mm²232 A181 A68.28 V (16.45%)346.7 V112.63 V (27.14%)82784.2 WDrop High
120 mm²269 A210 A54.05 V (13.03%)360.9 V89.16 V (21.49%)65537.5 WDrop High
150 mm²309 A241 A43.24 V (10.42%)371.8 V71.33 V (17.19%)52430.0 WDrop High
185 mm²353 A275 A35.06 V (8.45%)379.9 V57.84 V (13.94%)42510.8 WDrop High
240 mm²415 A324 A27.03 V (6.51%)388.0 V44.58 V (10.74%)32768.8 WDrop High
300 mm²477 A372 A21.62 V (5.21%)393.4 V35.67 V (8.59%)26215.0 WDrop High
400 mm²570 A445 A16.22 V (3.91%)398.8 V26.75 V (6.45%)19661.2 WDrop High

FAQ — 700 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 700A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 250m at 415V (voltage drop: 8.11V or 1.96%).

What is the power capacity of 700A at 415V?

At unity power factor, 700A at 415V supports 503.16 kW with a standard 700A circuit breaker.