700 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.35V (1.65%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 37.45V (5.43%)
Voltage at Load678.6 VLine Loss: 13762.9 W
Max Power & Breaker836.58 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6054.09 V (877.41%)0.0 V9986.43 V (1447.31%)7340200.0 WDrop High
2.5 mm²24 A18 A3632.46 V (526.44%)0.0 V5991.86 V (868.39%)4404120.0 WDrop High
4 mm²32 A25 A2270.29 V (329.03%)0.0 V3744.91 V (542.74%)2752575.0 WDrop High
6 mm²41 A32 A1513.52 V (219.35%)0.0 V2496.61 V (361.83%)1835050.0 WDrop High
10 mm²57 A44 A908.11 V (131.61%)0.0 V1497.96 V (217.1%)1101030.0 WDrop High
16 mm²76 A59 A567.57 V (82.26%)122.4 V936.23 V (135.69%)688143.7 WDrop High
25 mm²101 A78 A363.25 V (52.64%)326.8 V599.19 V (86.84%)440412.0 WDrop High
35 mm²125 A97 A259.46 V (37.6%)430.5 V427.99 V (62.03%)314580.0 WDrop High
50 mm²151 A118 A181.62 V (26.32%)508.4 V299.59 V (43.42%)220206.0 WDrop High
70 mm²192 A150 A129.73 V (18.8%)560.3 V213.99 V (31.01%)157290.0 WDrop High
95 mm²232 A181 A95.59 V (13.85%)594.4 V157.68 V (22.85%)115897.9 WDrop High
120 mm²269 A210 A75.68 V (10.97%)614.3 V124.83 V (18.09%)91752.5 WDrop High
150 mm²309 A241 A60.54 V (8.77%)629.5 V99.86 V (14.47%)73402.0 WDrop High
185 mm²353 A275 A49.09 V (7.11%)640.9 V80.97 V (11.73%)59515.1 WDrop High
240 mm²415 A324 A37.84 V (5.48%)652.2 V62.42 V (9.05%)45876.2 WDrop High
300 mm²477 A372 A30.27 V (4.39%)659.7 V49.93 V (7.24%)36701.0 WDrop High
400 mm²570 A445 A22.7 V (3.29%)667.3 V37.45 V (5.43%)27525.7 WDrop High

FAQ — 700 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 700A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 350m at 690V (voltage drop: 11.35V or 1.65%).

What is the power capacity of 700A at 690V?

At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.