900 Amp Cable Size at 90 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.75V (0.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.38V (2.98%)
Voltage at Load411.2 VLine Loss: 5850.2 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2001.56 V (482.3%)0.0 V3301.64 V (795.57%)3120120.0 WDrop High
2.5 mm²24 A18 A1200.93 V (289.38%)0.0 V1980.98 V (477.34%)1872072.0 WDrop High
4 mm²32 A25 A750.58 V (180.86%)0.0 V1238.11 V (298.34%)1170045.0 WDrop High
6 mm²41 A32 A500.39 V (120.58%)0.0 V825.41 V (198.89%)780030.0 WDrop High
10 mm²57 A44 A300.23 V (72.35%)114.8 V495.25 V (119.34%)468018.0 WDrop High
16 mm²76 A59 A187.65 V (45.22%)227.4 V309.53 V (74.59%)292511.2 WDrop High
25 mm²101 A78 A120.09 V (28.94%)294.9 V198.1 V (47.73%)187207.2 WDrop High
35 mm²125 A97 A85.78 V (20.67%)329.2 V141.5 V (34.1%)133719.4 WDrop High
50 mm²151 A118 A60.05 V (14.47%)355.0 V99.05 V (23.87%)93603.6 WDrop High
70 mm²192 A150 A42.89 V (10.34%)372.1 V70.75 V (17.05%)66859.7 WDrop High
95 mm²232 A181 A31.6 V (7.62%)383.4 V52.13 V (12.56%)49265.1 WDrop High
120 mm²269 A210 A25.02 V (6.03%)390.0 V41.27 V (9.94%)39001.5 WDrop High
150 mm²309 A241 A20.02 V (4.82%)395.0 V33.02 V (7.96%)31201.2 WDrop High
185 mm²353 A275 A16.23 V (3.91%)398.8 V26.77 V (6.45%)25298.3 WDrop High
240 mm²415 A324 A12.51 V (3.01%)402.5 V20.64 V (4.97%)19500.7 WDrop High
300 mm²477 A372 A10.01 V (2.41%)405.0 V16.51 V (3.98%)15600.6 WDrop High
400 mm²570 A445 A7.51 V (1.81%)407.5 V12.38 V (2.98%)11700.4 WDrop High

FAQ — 900 Amp Cable Size at 90 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 90 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 90m at 415V (voltage drop: 3.75V or 0.91%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.