Kabeltværsnit for 110 Ampere ved 5 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 5 m ved 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 0.67V (0.29%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 0.78V (0.34%)
Voltage at Load229.3 VLine Loss: 74.0 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A15.69 V (6.82%)214.3 V25.89 V (11.26%)1726.3 WDrop High
2.5 mm²24 A18 A9.42 V (4.09%)220.6 V15.53 V (6.75%)1035.8 WDrop High
4 mm²32 A25 A5.88 V (2.56%)224.1 V9.71 V (4.22%)647.4 WDrop High
6 mm²41 A32 A3.92 V (1.71%)226.1 V6.47 V (2.81%)431.6 WDrop High
10 mm²57 A44 A2.35 V (1.02%)227.6 V3.88 V (1.69%)258.9 WDrop High
16 mm²76 A59 A1.47 V (0.64%)228.5 V2.43 V (1.06%)161.8 WDrop High
25 mm²101 A78 A0.94 V (0.41%)229.1 V1.55 V (0.68%)103.6 WDrop High
35 mm²125 A97 A0.67 V (0.29%)229.3 V1.11 V (0.48%)74.0 W✓ OK (≤3%)
50 mm²151 A118 A0.47 V (0.2%)229.5 V0.78 V (0.34%)51.8 W✓ OK (≤3%)
70 mm²192 A150 A0.34 V (0.15%)229.7 V0.55 V (0.24%)37.0 W✓ OK (≤3%)
95 mm²232 A181 A0.25 V (0.11%)229.8 V0.41 V (0.18%)27.3 W✓ OK (≤3%)
120 mm²269 A210 A0.2 V (0.09%)229.8 V0.32 V (0.14%)21.6 W✓ OK (≤3%)
150 mm²309 A241 A0.16 V (0.07%)229.8 V0.26 V (0.11%)17.3 W✓ OK (≤3%)
185 mm²353 A275 A0.13 V (0.06%)229.9 V0.21 V (0.09%)14.0 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.04%)229.9 V0.16 V (0.07%)10.8 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.03%)229.9 V0.13 V (0.06%)8.6 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.03%)229.9 V0.1 V (0.04%)6.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 5 Meter (230V)

Hvilket kabeltværsnit kræves til 110A ved 5 meter (230V)?

Til 110 Ampere over 5 meter ved 230V anbefales 35 mm² kobberkabel (spændingsfald 0.67V / 0.29%).

Hvor mange kW svarer 110A ved 230V til?

Det svarer til 25.3 kW med en anbefalet sikring på 110A.