Kabeltværsnit for 110 Ampere ved 70 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 70 m ved 230V.
Copper Cable (≤3% Drop)50 mm²Drop: 6.59V (2.87%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 5.72V (2.49%)
Voltage at Load223.4 VLine Loss: 725.0 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 70m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 219.71 V (95.52%) | 10.3 V | 362.41 V (157.57%) | 24167.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 131.82 V (57.31%) | 98.2 V | 217.45 V (94.54%) | 14500.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 82.39 V (35.82%) | 147.6 V | 135.91 V (59.09%) | 9062.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 54.93 V (23.88%) | 175.1 V | 90.6 V (39.39%) | 6041.9 W | Drop High |
| 10 mm² | 57 A | 44 A | 32.96 V (14.33%) | 197.0 V | 54.36 V (23.64%) | 3625.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 20.6 V (8.96%) | 209.4 V | 33.98 V (14.77%) | 2265.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 13.18 V (5.73%) | 216.8 V | 21.74 V (9.45%) | 1450.1 W | Drop High |
| 35 mm² | 125 A | 97 A | 9.42 V (4.09%) | 220.6 V | 15.53 V (6.75%) | 1035.8 W | ~ ≤5% |
| 50 mm² | 151 A | 118 A | 6.59 V (2.87%) | 223.4 V | 10.87 V (4.73%) | 725.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 4.71 V (2.05%) | 225.3 V | 7.77 V (3.38%) | 517.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 3.47 V (1.51%) | 226.5 V | 5.72 V (2.49%) | 381.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 2.75 V (1.19%) | 227.3 V | 4.53 V (1.97%) | 302.1 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 2.2 V (0.96%) | 227.8 V | 3.62 V (1.58%) | 241.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.78 V (0.77%) | 228.2 V | 2.94 V (1.28%) | 196.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.37 V (0.6%) | 228.6 V | 2.27 V (0.98%) | 151.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.1 V (0.48%) | 228.9 V | 1.81 V (0.79%) | 120.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.82 V (0.36%) | 229.2 V | 1.36 V (0.59%) | 90.6 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 110 Ampere ved 70 Meter (230V)
Hvilket kabeltværsnit kræves til 110A ved 70 meter (230V)?
Til 110 Ampere over 70 meter ved 230V anbefales 50 mm² kobberkabel (spændingsfald 6.59V / 2.87%).
Hvor mange kW svarer 110A ved 230V til?
Det svarer til 25.3 kW med en anbefalet sikring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 10m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)10A · 70m (230V)16A · 70m (230V)20A · 70m (230V)25A · 70m (230V)32A · 70m (230V)40A · 70m (230V)50A · 70m (230V)63A · 70m (230V)80A · 70m (230V)100A · 70m (230V)125A · 70m (230V)160A · 70m (230V)200A · 70m (230V)