Kabeltværsnit for 110 Ampere ved 30 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 30 m ved 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 4.04V (1.75%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 4.66V (2.03%)
Voltage at Load226.0 VLine Loss: 443.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A94.16 V (40.94%)135.8 V155.32 V (67.53%)10357.6 WDrop High
2.5 mm²24 A18 A56.5 V (24.56%)173.5 V93.19 V (40.52%)6214.6 WDrop High
4 mm²32 A25 A35.31 V (15.35%)194.7 V58.24 V (25.32%)3884.1 WDrop High
6 mm²41 A32 A23.54 V (10.23%)206.5 V38.83 V (16.88%)2589.4 WDrop High
10 mm²57 A44 A14.12 V (6.14%)215.9 V23.3 V (10.13%)1553.6 WDrop High
16 mm²76 A59 A8.83 V (3.84%)221.2 V14.56 V (6.33%)971.0 WDrop High
25 mm²101 A78 A5.65 V (2.46%)224.4 V9.32 V (4.05%)621.5 WDrop High
35 mm²125 A97 A4.04 V (1.75%)226.0 V6.66 V (2.89%)443.9 W✓ OK (≤3%)
50 mm²151 A118 A2.82 V (1.23%)227.2 V4.66 V (2.03%)310.7 W✓ OK (≤3%)
70 mm²192 A150 A2.02 V (0.88%)228.0 V3.33 V (1.45%)221.9 W✓ OK (≤3%)
95 mm²232 A181 A1.49 V (0.65%)228.5 V2.45 V (1.07%)163.5 W✓ OK (≤3%)
120 mm²269 A210 A1.18 V (0.51%)228.8 V1.94 V (0.84%)129.5 W✓ OK (≤3%)
150 mm²309 A241 A0.94 V (0.41%)229.1 V1.55 V (0.68%)103.6 W✓ OK (≤3%)
185 mm²353 A275 A0.76 V (0.33%)229.2 V1.26 V (0.55%)84.0 W✓ OK (≤3%)
240 mm²415 A324 A0.59 V (0.26%)229.4 V0.97 V (0.42%)64.7 W✓ OK (≤3%)
300 mm²477 A372 A0.47 V (0.2%)229.5 V0.78 V (0.34%)51.8 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.15%)229.6 V0.58 V (0.25%)38.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 30 Meter (230V)

Hvilket kabeltværsnit kræves til 110A ved 30 meter (230V)?

Til 110 Ampere over 30 meter ved 230V anbefales 35 mm² kobberkabel (spændingsfald 4.04V / 1.75%).

Hvor mange kW svarer 110A ved 230V til?

Det svarer til 25.3 kW med en anbefalet sikring på 110A.