⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 110 Ampere ved 60 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 60 m ved 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 5.65V (2.46%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.66V (2.89%)
Voltage at Load224.4 VLine Loss: 621.5 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A188.32 V (81.88%)41.7 V310.64 V (135.06%)20715.2 WDrop High
2.5 mm²24 A18 A112.99 V (49.13%)117.0 V186.38 V (81.04%)12429.1 WDrop High
4 mm²32 A25 A70.62 V (30.7%)159.4 V116.49 V (50.65%)7768.2 WDrop High
6 mm²41 A32 A47.08 V (20.47%)182.9 V77.66 V (33.77%)5178.8 WDrop High
10 mm²57 A44 A28.25 V (12.28%)201.8 V46.6 V (20.26%)3107.3 WDrop High
16 mm²76 A59 A17.66 V (7.68%)212.3 V29.12 V (12.66%)1942.0 WDrop High
25 mm²101 A78 A11.3 V (4.91%)218.7 V18.64 V (8.1%)1242.9 WDrop High
35 mm²125 A97 A8.07 V (3.51%)221.9 V13.31 V (5.79%)887.8 W~ ≤5%
50 mm²151 A118 A5.65 V (2.46%)224.4 V9.32 V (4.05%)621.5 W✓ OK (≤3%)
70 mm²192 A150 A4.04 V (1.75%)226.0 V6.66 V (2.89%)443.9 W✓ OK (≤3%)
95 mm²232 A181 A2.97 V (1.29%)227.0 V4.9 V (2.13%)327.1 W✓ OK (≤3%)
120 mm²269 A210 A2.35 V (1.02%)227.6 V3.88 V (1.69%)258.9 W✓ OK (≤3%)
150 mm²309 A241 A1.88 V (0.82%)228.1 V3.11 V (1.35%)207.2 W✓ OK (≤3%)
185 mm²353 A275 A1.53 V (0.66%)228.5 V2.52 V (1.1%)168.0 W✓ OK (≤3%)
240 mm²415 A324 A1.18 V (0.51%)228.8 V1.94 V (0.84%)129.5 W✓ OK (≤3%)
300 mm²477 A372 A0.94 V (0.41%)229.1 V1.55 V (0.68%)103.6 W✓ OK (≤3%)
400 mm²570 A445 A0.71 V (0.31%)229.3 V1.16 V (0.51%)77.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 60 Meter (230V)

Hvilket kabeltværsnit kræves til 110A ved 60 meter (230V)?

Til 110 Ampere over 60 meter ved 230V anbefales 50 mm² kobberkabel (spændingsfald 5.65V / 2.46%).

Hvor mange kW svarer 110A ved 230V til?

Det svarer til 25.3 kW med en anbefalet sikring på 110A.