⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 110 Ampere ved 40 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 40 m ved 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 5.38V (2.34%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 6.21V (2.7%)
Voltage at Load224.6 VLine Loss: 591.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A125.55 V (54.59%)104.5 V207.09 V (90.04%)13810.1 WDrop High
2.5 mm²24 A18 A75.33 V (32.75%)154.7 V124.26 V (54.02%)8286.1 WDrop High
4 mm²32 A25 A47.08 V (20.47%)182.9 V77.66 V (33.77%)5178.8 WDrop High
6 mm²41 A32 A31.39 V (13.65%)198.6 V51.77 V (22.51%)3452.5 WDrop High
10 mm²57 A44 A18.83 V (8.19%)211.2 V31.06 V (13.51%)2071.5 WDrop High
16 mm²76 A59 A11.77 V (5.12%)218.2 V19.41 V (8.44%)1294.7 WDrop High
25 mm²101 A78 A7.53 V (3.28%)222.5 V12.43 V (5.4%)828.6 WDrop High
35 mm²125 A97 A5.38 V (2.34%)224.6 V8.88 V (3.86%)591.9 W✓ OK (≤3%)
50 mm²151 A118 A3.77 V (1.64%)226.2 V6.21 V (2.7%)414.3 W✓ OK (≤3%)
70 mm²192 A150 A2.69 V (1.17%)227.3 V4.44 V (1.93%)295.9 W✓ OK (≤3%)
95 mm²232 A181 A1.98 V (0.86%)228.0 V3.27 V (1.42%)218.1 W✓ OK (≤3%)
120 mm²269 A210 A1.57 V (0.68%)228.4 V2.59 V (1.13%)172.6 W✓ OK (≤3%)
150 mm²309 A241 A1.26 V (0.55%)228.7 V2.07 V (0.9%)138.1 W✓ OK (≤3%)
185 mm²353 A275 A1.02 V (0.44%)229.0 V1.68 V (0.73%)112.0 W✓ OK (≤3%)
240 mm²415 A324 A0.78 V (0.34%)229.2 V1.29 V (0.56%)86.3 W✓ OK (≤3%)
300 mm²477 A372 A0.63 V (0.27%)229.4 V1.04 V (0.45%)69.1 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.2%)229.5 V0.78 V (0.34%)51.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 40 Meter (230V)

Hvilket kabeltværsnit kræves til 110A ved 40 meter (230V)?

Til 110 Ampere over 40 meter ved 230V anbefales 35 mm² kobberkabel (spændingsfald 5.38V / 2.34%).

Hvor mange kW svarer 110A ved 230V til?

Det svarer til 25.3 kW med en anbefalet sikring på 110A.