⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 110 Ampere ved 10 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 10 m ved 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 1.35V (0.58%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 1.55V (0.68%)
Voltage at Load228.7 VLine Loss: 148.0 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A31.39 V (13.65%)198.6 V51.77 V (22.51%)3452.5 WDrop High
2.5 mm²24 A18 A18.83 V (8.19%)211.2 V31.06 V (13.51%)2071.5 WDrop High
4 mm²32 A25 A11.77 V (5.12%)218.2 V19.41 V (8.44%)1294.7 WDrop High
6 mm²41 A32 A7.85 V (3.41%)222.2 V12.94 V (5.63%)863.1 WDrop High
10 mm²57 A44 A4.71 V (2.05%)225.3 V7.77 V (3.38%)517.9 WDrop High
16 mm²76 A59 A2.94 V (1.28%)227.1 V4.85 V (2.11%)323.7 WDrop High
25 mm²101 A78 A1.88 V (0.82%)228.1 V3.11 V (1.35%)207.2 WDrop High
35 mm²125 A97 A1.35 V (0.58%)228.7 V2.22 V (0.96%)148.0 W✓ OK (≤3%)
50 mm²151 A118 A0.94 V (0.41%)229.1 V1.55 V (0.68%)103.6 W✓ OK (≤3%)
70 mm²192 A150 A0.67 V (0.29%)229.3 V1.11 V (0.48%)74.0 W✓ OK (≤3%)
95 mm²232 A181 A0.5 V (0.22%)229.5 V0.82 V (0.36%)54.5 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.17%)229.6 V0.65 V (0.28%)43.2 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.14%)229.7 V0.52 V (0.23%)34.5 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.11%)229.7 V0.42 V (0.18%)28.0 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.09%)229.8 V0.32 V (0.14%)21.6 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.07%)229.8 V0.26 V (0.11%)17.3 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.05%)229.9 V0.19 V (0.08%)12.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 10 Meter (230V)

Hvilket kabeltværsnit kræves til 110A ved 10 meter (230V)?

Til 110 Ampere over 10 meter ved 230V anbefales 35 mm² kobberkabel (spændingsfald 1.35V / 0.58%).

Hvor mange kW svarer 110A ved 230V til?

Det svarer til 25.3 kW med en anbefalet sikring på 110A.