Kabeltværsnit for 110 Ampere ved 10 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 10 m ved 230V.
Copper Cable (≤3% Drop)35 mm²Drop: 1.35V (0.58%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 1.55V (0.68%)
Voltage at Load228.7 VLine Loss: 148.0 W
Max Power & Breaker25.3 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 31.39 V (13.65%) | 198.6 V | 51.77 V (22.51%) | 3452.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 18.83 V (8.19%) | 211.2 V | 31.06 V (13.51%) | 2071.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 11.77 V (5.12%) | 218.2 V | 19.41 V (8.44%) | 1294.7 W | Drop High |
| 6 mm² | 41 A | 32 A | 7.85 V (3.41%) | 222.2 V | 12.94 V (5.63%) | 863.1 W | Drop High |
| 10 mm² | 57 A | 44 A | 4.71 V (2.05%) | 225.3 V | 7.77 V (3.38%) | 517.9 W | Drop High |
| 16 mm² | 76 A | 59 A | 2.94 V (1.28%) | 227.1 V | 4.85 V (2.11%) | 323.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 1.88 V (0.82%) | 228.1 V | 3.11 V (1.35%) | 207.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 1.35 V (0.58%) | 228.7 V | 2.22 V (0.96%) | 148.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.94 V (0.41%) | 229.1 V | 1.55 V (0.68%) | 103.6 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.67 V (0.29%) | 229.3 V | 1.11 V (0.48%) | 74.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.5 V (0.22%) | 229.5 V | 0.82 V (0.36%) | 54.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.39 V (0.17%) | 229.6 V | 0.65 V (0.28%) | 43.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.31 V (0.14%) | 229.7 V | 0.52 V (0.23%) | 34.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.25 V (0.11%) | 229.7 V | 0.42 V (0.18%) | 28.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.2 V (0.09%) | 229.8 V | 0.32 V (0.14%) | 21.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.16 V (0.07%) | 229.8 V | 0.26 V (0.11%) | 17.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.12 V (0.05%) | 229.9 V | 0.19 V (0.08%) | 12.9 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 110 Ampere ved 10 Meter (230V)
Hvilket kabeltværsnit kræves til 110A ved 10 meter (230V)?
Til 110 Ampere over 10 meter ved 230V anbefales 35 mm² kobberkabel (spændingsfald 1.35V / 0.58%).
Hvor mange kW svarer 110A ved 230V til?
Det svarer til 25.3 kW med en anbefalet sikring på 110A.
Related Lengths & Currents (230V)
110A · 5m (230V)110A · 15m (230V)110A · 20m (230V)110A · 25m (230V)110A · 30m (230V)110A · 35m (230V)110A · 40m (230V)110A · 45m (230V)110A · 50m (230V)110A · 60m (230V)110A · 70m (230V)10A · 10m (230V)16A · 10m (230V)20A · 10m (230V)25A · 10m (230V)32A · 10m (230V)40A · 10m (230V)50A · 10m (230V)63A · 10m (230V)80A · 10m (230V)100A · 10m (230V)125A · 10m (230V)160A · 10m (230V)200A · 10m (230V)