Kabeltværsnit for 110 Ampere ved 15 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 15 m ved 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 2.02V (0.88%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 2.33V (1.01%)
Voltage at Load228.0 VLine Loss: 221.9 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A47.08 V (20.47%)182.9 V77.66 V (33.77%)5178.8 WDrop High
2.5 mm²24 A18 A28.25 V (12.28%)201.8 V46.6 V (20.26%)3107.3 WDrop High
4 mm²32 A25 A17.66 V (7.68%)212.3 V29.12 V (12.66%)1942.0 WDrop High
6 mm²41 A32 A11.77 V (5.12%)218.2 V19.41 V (8.44%)1294.7 WDrop High
10 mm²57 A44 A7.06 V (3.07%)222.9 V11.65 V (5.06%)776.8 WDrop High
16 mm²76 A59 A4.41 V (1.92%)225.6 V7.28 V (3.17%)485.5 WDrop High
25 mm²101 A78 A2.82 V (1.23%)227.2 V4.66 V (2.03%)310.7 WDrop High
35 mm²125 A97 A2.02 V (0.88%)228.0 V3.33 V (1.45%)221.9 W✓ OK (≤3%)
50 mm²151 A118 A1.41 V (0.61%)228.6 V2.33 V (1.01%)155.4 W✓ OK (≤3%)
70 mm²192 A150 A1.01 V (0.44%)229.0 V1.66 V (0.72%)111.0 W✓ OK (≤3%)
95 mm²232 A181 A0.74 V (0.32%)229.3 V1.23 V (0.53%)81.8 W✓ OK (≤3%)
120 mm²269 A210 A0.59 V (0.26%)229.4 V0.97 V (0.42%)64.7 W✓ OK (≤3%)
150 mm²309 A241 A0.47 V (0.2%)229.5 V0.78 V (0.34%)51.8 W✓ OK (≤3%)
185 mm²353 A275 A0.38 V (0.17%)229.6 V0.63 V (0.27%)42.0 W✓ OK (≤3%)
240 mm²415 A324 A0.29 V (0.13%)229.7 V0.49 V (0.21%)32.4 W✓ OK (≤3%)
300 mm²477 A372 A0.24 V (0.1%)229.8 V0.39 V (0.17%)25.9 W✓ OK (≤3%)
400 mm²570 A445 A0.18 V (0.08%)229.8 V0.29 V (0.13%)19.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 15 Meter (230V)

Hvilket kabeltværsnit kræves til 110A ved 15 meter (230V)?

Til 110 Ampere over 15 meter ved 230V anbefales 35 mm² kobberkabel (spændingsfald 2.02V / 0.88%).

Hvor mange kW svarer 110A ved 230V til?

Det svarer til 25.3 kW med en anbefalet sikring på 110A.