Kabeltværsnit for 110 Ampere ved 80 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 80 m ved 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 9.32V (2.33%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 10.76V (2.69%)
Voltage at Load390.7 VLine Loss: 1775.6 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A217.45 V (54.36%)182.5 V358.7 V (89.67%)41430.4 WDrop High
2.5 mm²24 A18 A130.47 V (32.62%)269.5 V215.22 V (53.8%)24858.2 WDrop High
4 mm²32 A25 A81.54 V (20.39%)318.5 V134.51 V (33.63%)15536.4 WDrop High
6 mm²41 A32 A54.36 V (13.59%)345.6 V89.67 V (22.42%)10357.6 WDrop High
10 mm²57 A44 A32.62 V (8.15%)367.4 V53.8 V (13.45%)6214.6 WDrop High
16 mm²76 A59 A20.39 V (5.1%)379.6 V33.63 V (8.41%)3884.1 WDrop High
25 mm²101 A78 A13.05 V (3.26%)387.0 V21.52 V (5.38%)2485.8 WDrop High
35 mm²125 A97 A9.32 V (2.33%)390.7 V15.37 V (3.84%)1775.6 W✓ OK (≤3%)
50 mm²151 A118 A6.52 V (1.63%)393.5 V10.76 V (2.69%)1242.9 W✓ OK (≤3%)
70 mm²192 A150 A4.66 V (1.16%)395.3 V7.69 V (1.92%)887.8 W✓ OK (≤3%)
95 mm²232 A181 A3.43 V (0.86%)396.6 V5.66 V (1.42%)654.2 W✓ OK (≤3%)
120 mm²269 A210 A2.72 V (0.68%)397.3 V4.48 V (1.12%)517.9 W✓ OK (≤3%)
150 mm²309 A241 A2.17 V (0.54%)397.8 V3.59 V (0.9%)414.3 W✓ OK (≤3%)
185 mm²353 A275 A1.76 V (0.44%)398.2 V2.91 V (0.73%)335.9 W✓ OK (≤3%)
240 mm²415 A324 A1.36 V (0.34%)398.6 V2.24 V (0.56%)258.9 W✓ OK (≤3%)
300 mm²477 A372 A1.09 V (0.27%)398.9 V1.79 V (0.45%)207.2 W✓ OK (≤3%)
400 mm²570 A445 A0.82 V (0.2%)399.2 V1.35 V (0.34%)155.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 80 Meter (400V)

Hvilket kabeltværsnit kræves til 110A ved 80 meter (400V)?

Til 110 Ampere over 80 meter ved 400V anbefales 35 mm² kobberkabel (spændingsfald 9.32V / 2.33%).

Hvor mange kW svarer 110A ved 400V til?

Det svarer til 76.21 kW med en anbefalet sikring på 110A.