⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 475 Ampere ved 90 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 475 A over 90 m ved 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 6.1V (2.65%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.55V (3.28%)
Voltage at Load223.9 VLine Loss: 2897.0 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1219.8 V (530.35%)0.0 V2012.1 V (874.83%)579405.0 WDrop High
2.5 mm²24 A18 A731.88 V (318.21%)0.0 V1207.26 V (524.9%)347643.0 WDrop High
4 mm²32 A25 A457.43 V (198.88%)0.0 V754.54 V (328.06%)217276.9 WDrop High
6 mm²41 A32 A304.95 V (132.59%)0.0 V503.02 V (218.71%)144851.2 WDrop High
10 mm²57 A44 A182.97 V (79.55%)47.0 V301.81 V (131.22%)86910.8 WDrop High
16 mm²76 A59 A114.36 V (49.72%)115.6 V188.63 V (82.01%)54319.2 WDrop High
25 mm²101 A78 A73.19 V (31.82%)156.8 V120.73 V (52.49%)34764.3 WDrop High
35 mm²125 A97 A52.28 V (22.73%)177.7 V86.23 V (37.49%)24831.6 WDrop High
50 mm²151 A118 A36.59 V (15.91%)193.4 V60.36 V (26.24%)17382.1 WDrop High
70 mm²192 A150 A26.14 V (11.36%)203.9 V43.12 V (18.75%)12415.8 WDrop High
95 mm²232 A181 A19.26 V (8.37%)210.7 V31.77 V (13.81%)9148.5 WDrop High
120 mm²269 A210 A15.25 V (6.63%)214.8 V25.15 V (10.94%)7242.6 WDrop High
150 mm²309 A241 A12.2 V (5.3%)217.8 V20.12 V (8.75%)5794.0 WDrop High
185 mm²353 A275 A9.89 V (4.3%)220.1 V16.31 V (7.09%)4697.9 WDrop High
240 mm²415 A324 A7.62 V (3.31%)222.4 V12.58 V (5.47%)3621.3 WDrop High
300 mm²477 A372 A6.1 V (2.65%)223.9 V10.06 V (4.37%)2897.0 W✓ OK (≤3%)
400 mm²570 A445 A4.57 V (1.99%)225.4 V7.55 V (3.28%)2172.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 475 Ampere ved 90 Meter (230V)

Hvilket kabeltværsnit kræves til 475A ved 90 meter (230V)?

Til 475 Ampere over 90 meter ved 230V anbefales 300 mm² kobberkabel (spændingsfald 6.1V / 2.65%).

Hvor mange kW svarer 475A ved 230V til?

Det svarer til 109.25 kW med en anbefalet sikring på 500A.