Kabelarea för 110 Ampere vid 500 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 500 m vid 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 11.02V (2.75%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 11.21V (2.8%)
Voltage at Load389.0 VLine Loss: 2099.5 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1359.08 V (339.77%)0.0 V2241.85 V (560.46%)258940.0 WDrop High
2.5 mm²24 A18 A815.45 V (203.86%)0.0 V1345.11 V (336.28%)155364.0 WDrop High
4 mm²32 A25 A509.66 V (127.41%)0.0 V840.69 V (210.17%)97102.5 WDrop High
6 mm²41 A32 A339.77 V (84.94%)60.2 V560.46 V (140.12%)64735.0 WDrop High
10 mm²57 A44 A203.86 V (50.97%)196.1 V336.28 V (84.07%)38841.0 WDrop High
16 mm²76 A59 A127.41 V (31.85%)272.6 V210.17 V (52.54%)24275.6 WDrop High
25 mm²101 A78 A81.54 V (20.39%)318.5 V134.51 V (33.63%)15536.4 WDrop High
35 mm²125 A97 A58.25 V (14.56%)341.8 V96.08 V (24.02%)11097.4 WDrop High
50 mm²151 A118 A40.77 V (10.19%)359.2 V67.26 V (16.81%)7768.2 WDrop High
70 mm²192 A150 A29.12 V (7.28%)370.9 V48.04 V (12.01%)5548.7 WDrop High
95 mm²232 A181 A21.46 V (5.36%)378.5 V35.4 V (8.85%)4088.5 WDrop High
120 mm²269 A210 A16.99 V (4.25%)383.0 V28.02 V (7.01%)3236.7 W~ ≤5%
150 mm²309 A241 A13.59 V (3.4%)386.4 V22.42 V (5.6%)2589.4 W~ ≤5%
185 mm²353 A275 A11.02 V (2.75%)389.0 V18.18 V (4.54%)2099.5 W✓ OK (≤3%)
240 mm²415 A324 A8.49 V (2.12%)391.5 V14.01 V (3.5%)1618.4 W✓ OK (≤3%)
300 mm²477 A372 A6.8 V (1.7%)393.2 V11.21 V (2.8%)1294.7 W✓ OK (≤3%)
400 mm²570 A445 A5.1 V (1.27%)394.9 V8.41 V (2.1%)971.0 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 500 Meter (400V)

Vilken kabelarea krävs för 110A vid 500 meter (400V)?

För 110 Ampere över 500 meter vid 400V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (11.02V / 2.75%).

Hur stor effekt motsvarar 110A vid 400V?

Det motsvarar 76.21 kW med en rekommenderad säkring på 110A.