Kabelarea för 35 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 35 A över 120 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 10.27V (2.57%)
Voltage at Load390.3 VLine Loss: 589.8 W
Max Power & Breaker24.25 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A103.78 V (25.95%)296.2 V171.2 V (42.8%)6291.6 WDrop High
2.5 mm²24 A18 A62.27 V (15.57%)337.7 V102.72 V (25.68%)3775.0 WDrop High
4 mm²32 A25 A38.92 V (9.73%)361.1 V64.2 V (16.05%)2359.3 WDrop High
6 mm²41 A32 A25.95 V (6.49%)374.1 V42.8 V (10.7%)1572.9 WDrop High
10 mm²57 A44 A15.57 V (3.89%)384.4 V25.68 V (6.42%)943.7 W~ ≤5%
16 mm²76 A59 A9.73 V (2.43%)390.3 V16.05 V (4.01%)589.8 W✓ OK (≤3%)
25 mm²101 A78 A6.23 V (1.56%)393.8 V10.27 V (2.57%)377.5 W✓ OK (≤3%)
35 mm²125 A97 A4.45 V (1.11%)395.6 V7.34 V (1.83%)269.6 W✓ OK (≤3%)
50 mm²151 A118 A3.11 V (0.78%)396.9 V5.14 V (1.28%)188.7 W✓ OK (≤3%)
70 mm²192 A150 A2.22 V (0.56%)397.8 V3.67 V (0.92%)134.8 W✓ OK (≤3%)
95 mm²232 A181 A1.64 V (0.41%)398.4 V2.7 V (0.68%)99.3 W✓ OK (≤3%)
120 mm²269 A210 A1.3 V (0.32%)398.7 V2.14 V (0.53%)78.6 W✓ OK (≤3%)
150 mm²309 A241 A1.04 V (0.26%)399.0 V1.71 V (0.43%)62.9 W✓ OK (≤3%)
185 mm²353 A275 A0.84 V (0.21%)399.2 V1.39 V (0.35%)51.0 W✓ OK (≤3%)
240 mm²415 A324 A0.65 V (0.16%)399.4 V1.07 V (0.27%)39.3 W✓ OK (≤3%)
300 mm²477 A372 A0.52 V (0.13%)399.5 V0.86 V (0.21%)31.5 W✓ OK (≤3%)
400 mm²570 A445 A0.39 V (0.1%)399.6 V0.64 V (0.16%)23.6 W✓ OK (≤3%)

FAQ — Kabelarea för 35 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 35A vid 120 meter (400V)?

För 35 Ampere över 120 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (9.73V / 2.43%).

Hur stor effekt motsvarar 35A vid 400V?

Det motsvarar 24.25 kW med en rekommenderad säkring på 35A.