Kabelarea för 425 Ampere vid 40 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 40 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.1V (0.53%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.6V (0.65%)
Voltage at Load397.9 VLine Loss: 1546.1 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A420.08 V (105.02%)0.0 V692.94 V (173.23%)309230.0 WDrop High
2.5 mm²24 A18 A252.05 V (63.01%)148.0 V415.76 V (103.94%)185538.0 WDrop High
4 mm²32 A25 A157.53 V (39.38%)242.5 V259.85 V (64.96%)115961.2 WDrop High
6 mm²41 A32 A105.02 V (26.26%)295.0 V173.23 V (43.31%)77307.5 WDrop High
10 mm²57 A44 A63.01 V (15.75%)337.0 V103.94 V (25.99%)46384.5 WDrop High
16 mm²76 A59 A39.38 V (9.85%)360.6 V64.96 V (16.24%)28990.3 WDrop High
25 mm²101 A78 A25.2 V (6.3%)374.8 V41.58 V (10.39%)18553.8 WDrop High
35 mm²125 A97 A18.0 V (4.5%)382.0 V29.7 V (7.42%)13252.7 WDrop High
50 mm²151 A118 A12.6 V (3.15%)387.4 V20.79 V (5.2%)9276.9 WDrop High
70 mm²192 A150 A9.0 V (2.25%)391.0 V14.85 V (3.71%)6626.4 WDrop High
95 mm²232 A181 A6.63 V (1.66%)393.4 V10.94 V (2.74%)4882.6 WDrop High
120 mm²269 A210 A5.25 V (1.31%)394.7 V8.66 V (2.17%)3865.4 WDrop High
150 mm²309 A241 A4.2 V (1.05%)395.8 V6.93 V (1.73%)3092.3 WDrop High
185 mm²353 A275 A3.41 V (0.85%)396.6 V5.62 V (1.4%)2507.3 WDrop High
240 mm²415 A324 A2.63 V (0.66%)397.4 V4.33 V (1.08%)1932.7 WDrop High
300 mm²477 A372 A2.1 V (0.53%)397.9 V3.46 V (0.87%)1546.1 W✓ OK (≤3%)
400 mm²570 A445 A1.58 V (0.39%)398.4 V2.6 V (0.65%)1159.6 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 40 Meter (400V)

Vilken kabelarea krävs för 425A vid 40 meter (400V)?

För 425 Ampere över 40 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.1V / 0.53%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.