Kabelarea för 425 Ampere vid 30 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 30 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.58V (0.39%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.95V (0.49%)
Voltage at Load398.4 VLine Loss: 1159.6 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A315.06 V (78.77%)84.9 V519.7 V (129.93%)231922.5 WDrop High
2.5 mm²24 A18 A189.04 V (47.26%)211.0 V311.82 V (77.96%)139153.5 WDrop High
4 mm²32 A25 A118.15 V (29.54%)281.9 V194.89 V (48.72%)86970.9 WDrop High
6 mm²41 A32 A78.77 V (19.69%)321.2 V129.93 V (32.48%)57980.6 WDrop High
10 mm²57 A44 A47.26 V (11.81%)352.7 V77.96 V (19.49%)34788.4 WDrop High
16 mm²76 A59 A29.54 V (7.38%)370.5 V48.72 V (12.18%)21742.7 WDrop High
25 mm²101 A78 A18.9 V (4.73%)381.1 V31.18 V (7.8%)13915.4 WDrop High
35 mm²125 A97 A13.5 V (3.38%)386.5 V22.27 V (5.57%)9939.5 WDrop High
50 mm²151 A118 A9.45 V (2.36%)390.5 V15.59 V (3.9%)6957.7 WDrop High
70 mm²192 A150 A6.75 V (1.69%)393.2 V11.14 V (2.78%)4969.8 WDrop High
95 mm²232 A181 A4.97 V (1.24%)395.0 V8.21 V (2.05%)3661.9 WDrop High
120 mm²269 A210 A3.94 V (0.98%)396.1 V6.5 V (1.62%)2899.0 WDrop High
150 mm²309 A241 A3.15 V (0.79%)396.8 V5.2 V (1.3%)2319.2 WDrop High
185 mm²353 A275 A2.55 V (0.64%)397.4 V4.21 V (1.05%)1880.5 WDrop High
240 mm²415 A324 A1.97 V (0.49%)398.0 V3.25 V (0.81%)1449.5 WDrop High
300 mm²477 A372 A1.58 V (0.39%)398.4 V2.6 V (0.65%)1159.6 W✓ OK (≤3%)
400 mm²570 A445 A1.18 V (0.3%)398.8 V1.95 V (0.49%)869.7 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 30 Meter (400V)

Vilken kabelarea krävs för 425A vid 30 meter (400V)?

För 425 Ampere över 30 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (1.58V / 0.39%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.