Kabelarea för 425 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 60 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 3.15V (0.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.9V (0.97%)
Voltage at Load396.8 VLine Loss: 2319.2 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A630.12 V (157.53%)0.0 V1039.4 V (259.85%)463845.0 WDrop High
2.5 mm²24 A18 A378.07 V (94.52%)21.9 V623.64 V (155.91%)278307.0 WDrop High
4 mm²32 A25 A236.3 V (59.07%)163.7 V389.78 V (97.44%)173941.9 WDrop High
6 mm²41 A32 A157.53 V (39.38%)242.5 V259.85 V (64.96%)115961.2 WDrop High
10 mm²57 A44 A94.52 V (23.63%)305.5 V155.91 V (38.98%)69576.8 WDrop High
16 mm²76 A59 A59.07 V (14.77%)340.9 V97.44 V (24.36%)43485.5 WDrop High
25 mm²101 A78 A37.81 V (9.45%)362.2 V62.36 V (15.59%)27830.7 WDrop High
35 mm²125 A97 A27.01 V (6.75%)373.0 V44.55 V (11.14%)19879.1 WDrop High
50 mm²151 A118 A18.9 V (4.73%)381.1 V31.18 V (7.8%)13915.4 WDrop High
70 mm²192 A150 A13.5 V (3.38%)386.5 V22.27 V (5.57%)9939.5 WDrop High
95 mm²232 A181 A9.95 V (2.49%)390.1 V16.41 V (4.1%)7323.9 WDrop High
120 mm²269 A210 A7.88 V (1.97%)392.1 V12.99 V (3.25%)5798.1 WDrop High
150 mm²309 A241 A6.3 V (1.58%)393.7 V10.39 V (2.6%)4638.4 WDrop High
185 mm²353 A275 A5.11 V (1.28%)394.9 V8.43 V (2.11%)3760.9 WDrop High
240 mm²415 A324 A3.94 V (0.98%)396.1 V6.5 V (1.62%)2899.0 WDrop High
300 mm²477 A372 A3.15 V (0.79%)396.8 V5.2 V (1.3%)2319.2 W✓ OK (≤3%)
400 mm²570 A445 A2.36 V (0.59%)397.6 V3.9 V (0.97%)1739.4 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 425A vid 60 meter (400V)?

För 425 Ampere över 60 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (3.15V / 0.79%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.