Kabelarea för 425 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 35 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.84V (0.46%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.27V (0.57%)
Voltage at Load398.2 VLine Loss: 1352.9 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A367.57 V (91.89%)32.4 V606.32 V (151.58%)270576.2 WDrop High
2.5 mm²24 A18 A220.54 V (55.14%)179.5 V363.79 V (90.95%)162345.8 WDrop High
4 mm²32 A25 A137.84 V (34.46%)262.2 V227.37 V (56.84%)101466.1 WDrop High
6 mm²41 A32 A91.89 V (22.97%)308.1 V151.58 V (37.89%)67644.1 WDrop High
10 mm²57 A44 A55.14 V (13.78%)344.9 V90.95 V (22.74%)40586.4 WDrop High
16 mm²76 A59 A34.46 V (8.61%)365.5 V56.84 V (14.21%)25366.5 WDrop High
25 mm²101 A78 A22.05 V (5.51%)377.9 V36.38 V (9.09%)16234.6 WDrop High
35 mm²125 A97 A15.75 V (3.94%)384.2 V25.99 V (6.5%)11596.1 WDrop High
50 mm²151 A118 A11.03 V (2.76%)389.0 V18.19 V (4.55%)8117.3 WDrop High
70 mm²192 A150 A7.88 V (1.97%)392.1 V12.99 V (3.25%)5798.1 WDrop High
95 mm²232 A181 A5.8 V (1.45%)394.2 V9.57 V (2.39%)4272.3 WDrop High
120 mm²269 A210 A4.59 V (1.15%)395.4 V7.58 V (1.89%)3382.2 WDrop High
150 mm²309 A241 A3.68 V (0.92%)396.3 V6.06 V (1.52%)2705.8 WDrop High
185 mm²353 A275 A2.98 V (0.75%)397.0 V4.92 V (1.23%)2193.9 WDrop High
240 mm²415 A324 A2.3 V (0.57%)397.7 V3.79 V (0.95%)1691.1 WDrop High
300 mm²477 A372 A1.84 V (0.46%)398.2 V3.03 V (0.76%)1352.9 W✓ OK (≤3%)
400 mm²570 A445 A1.38 V (0.34%)398.6 V2.27 V (0.57%)1014.7 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 425A vid 35 meter (400V)?

För 425 Ampere över 35 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (1.84V / 0.46%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.