Kabelarea för 425 Ampere vid 15 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 15 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 0.79V (0.2%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.97V (0.24%)
Voltage at Load399.2 VLine Loss: 579.8 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A157.53 V (39.38%)242.5 V259.85 V (64.96%)115961.2 WDrop High
2.5 mm²24 A18 A94.52 V (23.63%)305.5 V155.91 V (38.98%)69576.8 WDrop High
4 mm²32 A25 A59.07 V (14.77%)340.9 V97.44 V (24.36%)43485.5 WDrop High
6 mm²41 A32 A39.38 V (9.85%)360.6 V64.96 V (16.24%)28990.3 WDrop High
10 mm²57 A44 A23.63 V (5.91%)376.4 V38.98 V (9.74%)17394.2 WDrop High
16 mm²76 A59 A14.77 V (3.69%)385.2 V24.36 V (6.09%)10871.4 WDrop High
25 mm²101 A78 A9.45 V (2.36%)390.5 V15.59 V (3.9%)6957.7 WDrop High
35 mm²125 A97 A6.75 V (1.69%)393.2 V11.14 V (2.78%)4969.8 WDrop High
50 mm²151 A118 A4.73 V (1.18%)395.3 V7.8 V (1.95%)3478.8 WDrop High
70 mm²192 A150 A3.38 V (0.84%)396.6 V5.57 V (1.39%)2484.9 WDrop High
95 mm²232 A181 A2.49 V (0.62%)397.5 V4.1 V (1.03%)1831.0 WDrop High
120 mm²269 A210 A1.97 V (0.49%)398.0 V3.25 V (0.81%)1449.5 WDrop High
150 mm²309 A241 A1.58 V (0.39%)398.4 V2.6 V (0.65%)1159.6 WDrop High
185 mm²353 A275 A1.28 V (0.32%)398.7 V2.11 V (0.53%)940.2 WDrop High
240 mm²415 A324 A0.98 V (0.25%)399.0 V1.62 V (0.41%)724.8 WDrop High
300 mm²477 A372 A0.79 V (0.2%)399.2 V1.3 V (0.32%)579.8 W✓ OK (≤3%)
400 mm²570 A445 A0.59 V (0.15%)399.4 V0.97 V (0.24%)434.9 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 15 Meter (400V)

Vilken kabelarea krävs för 425A vid 15 meter (400V)?

För 425 Ampere över 15 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (0.79V / 0.2%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.