Kabelarea för 425 Ampere vid 70 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 70 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 3.68V (0.92%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.55V (1.14%)
Voltage at Load396.3 VLine Loss: 2705.8 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A735.14 V (183.79%)0.0 V1212.64 V (303.16%)541152.5 WDrop High
2.5 mm²24 A18 A441.08 V (110.27%)0.0 V727.58 V (181.9%)324691.5 WDrop High
4 mm²32 A25 A275.68 V (68.92%)124.3 V454.74 V (113.68%)202932.2 WDrop High
6 mm²41 A32 A183.79 V (45.95%)216.2 V303.16 V (75.79%)135288.1 WDrop High
10 mm²57 A44 A110.27 V (27.57%)289.7 V181.9 V (45.47%)81172.9 WDrop High
16 mm²76 A59 A68.92 V (17.23%)331.1 V113.68 V (28.42%)50733.0 WDrop High
25 mm²101 A78 A44.11 V (11.03%)355.9 V72.76 V (18.19%)32469.2 WDrop High
35 mm²125 A97 A31.51 V (7.88%)368.5 V51.97 V (12.99%)23192.2 WDrop High
50 mm²151 A118 A22.05 V (5.51%)377.9 V36.38 V (9.09%)16234.6 WDrop High
70 mm²192 A150 A15.75 V (3.94%)384.2 V25.99 V (6.5%)11596.1 WDrop High
95 mm²232 A181 A11.61 V (2.9%)388.4 V19.15 V (4.79%)8544.5 WDrop High
120 mm²269 A210 A9.19 V (2.3%)390.8 V15.16 V (3.79%)6764.4 WDrop High
150 mm²309 A241 A7.35 V (1.84%)392.6 V12.13 V (3.03%)5411.5 WDrop High
185 mm²353 A275 A5.96 V (1.49%)394.0 V9.83 V (2.46%)4387.7 WDrop High
240 mm²415 A324 A4.59 V (1.15%)395.4 V7.58 V (1.89%)3382.2 WDrop High
300 mm²477 A372 A3.68 V (0.92%)396.3 V6.06 V (1.52%)2705.8 W✓ OK (≤3%)
400 mm²570 A445 A2.76 V (0.69%)397.2 V4.55 V (1.14%)2029.3 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 70 Meter (400V)

Vilken kabelarea krävs för 425A vid 70 meter (400V)?

För 425 Ampere över 70 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (3.68V / 0.92%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.