Kabelarea för 425 Ampere vid 400 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 400 m vid 230V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 6.06V (2.64%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 30.0V (13.05%)
Voltage at Load223.9 VLine Loss: 2576.9 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4850.67 V (2108.99%)0.0 V8001.33 V (3478.84%)2061533.3 WDrop High
2.5 mm²24 A18 A2910.4 V (1265.39%)0.0 V4800.8 V (2087.3%)1236920.0 WDrop High
4 mm²32 A25 A1819.0 V (790.87%)0.0 V3000.5 V (1304.57%)773075.0 WDrop High
6 mm²41 A32 A1212.67 V (527.25%)0.0 V2000.33 V (869.71%)515383.3 WDrop High
10 mm²57 A44 A727.6 V (316.35%)0.0 V1200.2 V (521.83%)309230.0 WDrop High
16 mm²76 A59 A454.75 V (197.72%)0.0 V750.12 V (326.14%)193268.7 WDrop High
25 mm²101 A78 A291.04 V (126.54%)0.0 V480.08 V (208.73%)123692.0 WDrop High
35 mm²125 A97 A207.89 V (90.39%)22.1 V342.91 V (149.09%)88351.4 WDrop High
50 mm²151 A118 A145.52 V (63.27%)84.5 V240.04 V (104.37%)61846.0 WDrop High
70 mm²192 A150 A103.94 V (45.19%)126.1 V171.46 V (74.55%)44175.7 WDrop High
95 mm²232 A181 A76.59 V (33.3%)153.4 V126.34 V (54.93%)32550.5 WDrop High
120 mm²269 A210 A60.63 V (26.36%)169.4 V100.02 V (43.49%)25769.2 WDrop High
150 mm²309 A241 A48.51 V (21.09%)181.5 V80.01 V (34.79%)20615.3 WDrop High
185 mm²353 A275 A39.33 V (17.1%)190.7 V64.88 V (28.21%)16715.1 WDrop High
240 mm²415 A324 A30.32 V (13.18%)199.7 V50.01 V (21.74%)12884.6 WDrop High
300 mm²477 A372 A24.25 V (10.54%)205.7 V40.01 V (17.39%)10307.7 WDrop High
400 mm²570 A445 A18.19 V (7.91%)211.8 V30.0 V (13.05%)7730.7 WDrop High

FAQ — Kabelarea för 425 Ampere vid 400 Meter (230V)

Vilken kabelarea krävs för 425A vid 400 meter (230V)?

För 425 Ampere över 400 meter vid 230V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.06V / 2.64%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.