Kabelarea för 425 Ampere vid 400 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 400 m vid 230V.
Copper Cable (≤3% Drop)3× 400 mm²Drop: 6.06V (2.64%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 30.0V (13.05%)
Voltage at Load223.9 VLine Loss: 2576.9 W
Max Power & Breaker97.75 kW450A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 400m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 4850.67 V (2108.99%) | 0.0 V | 8001.33 V (3478.84%) | 2061533.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2910.4 V (1265.39%) | 0.0 V | 4800.8 V (2087.3%) | 1236920.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1819.0 V (790.87%) | 0.0 V | 3000.5 V (1304.57%) | 773075.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 1212.67 V (527.25%) | 0.0 V | 2000.33 V (869.71%) | 515383.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 727.6 V (316.35%) | 0.0 V | 1200.2 V (521.83%) | 309230.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 454.75 V (197.72%) | 0.0 V | 750.12 V (326.14%) | 193268.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 291.04 V (126.54%) | 0.0 V | 480.08 V (208.73%) | 123692.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 207.89 V (90.39%) | 22.1 V | 342.91 V (149.09%) | 88351.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 145.52 V (63.27%) | 84.5 V | 240.04 V (104.37%) | 61846.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 103.94 V (45.19%) | 126.1 V | 171.46 V (74.55%) | 44175.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 76.59 V (33.3%) | 153.4 V | 126.34 V (54.93%) | 32550.5 W | Drop High |
| 120 mm² | 269 A | 210 A | 60.63 V (26.36%) | 169.4 V | 100.02 V (43.49%) | 25769.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 48.51 V (21.09%) | 181.5 V | 80.01 V (34.79%) | 20615.3 W | Drop High |
| 185 mm² | 353 A | 275 A | 39.33 V (17.1%) | 190.7 V | 64.88 V (28.21%) | 16715.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 30.32 V (13.18%) | 199.7 V | 50.01 V (21.74%) | 12884.6 W | Drop High |
| 300 mm² | 477 A | 372 A | 24.25 V (10.54%) | 205.7 V | 40.01 V (17.39%) | 10307.7 W | Drop High |
| 400 mm² | 570 A | 445 A | 18.19 V (7.91%) | 211.8 V | 30.0 V (13.05%) | 7730.7 W | Drop High |
FAQ — Kabelarea för 425 Ampere vid 400 Meter (230V)
Vilken kabelarea krävs för 425A vid 400 meter (230V)?
För 425 Ampere över 400 meter vid 230V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.06V / 2.64%).
Hur stor effekt motsvarar 425A vid 230V?
Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.
Related Lengths & Currents (230V)
425A · 5m (230V)425A · 10m (230V)425A · 15m (230V)425A · 20m (230V)425A · 25m (230V)425A · 30m (230V)425A · 35m (230V)425A · 40m (230V)425A · 45m (230V)425A · 50m (230V)425A · 60m (230V)425A · 70m (230V)10A · 400m (230V)16A · 400m (230V)20A · 400m (230V)25A · 400m (230V)32A · 400m (230V)40A · 400m (230V)50A · 400m (230V)63A · 400m (230V)80A · 400m (230V)100A · 400m (230V)125A · 400m (230V)160A · 400m (230V)200A · 400m (230V)