⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 425 Ampere vid 90 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 90 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 5.46V (2.37%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.75V (2.94%)
Voltage at Load224.5 VLine Loss: 2319.2 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1091.4 V (474.52%)0.0 V1800.3 V (782.74%)463845.0 WDrop High
2.5 mm²24 A18 A654.84 V (284.71%)0.0 V1080.18 V (469.64%)278307.0 WDrop High
4 mm²32 A25 A409.27 V (177.95%)0.0 V675.11 V (293.53%)173941.9 WDrop High
6 mm²41 A32 A272.85 V (118.63%)0.0 V450.07 V (195.68%)115961.2 WDrop High
10 mm²57 A44 A163.71 V (71.18%)66.3 V270.04 V (117.41%)69576.8 WDrop High
16 mm²76 A59 A102.32 V (44.49%)127.7 V168.78 V (73.38%)43485.5 WDrop High
25 mm²101 A78 A65.48 V (28.47%)164.5 V108.02 V (46.96%)27830.7 WDrop High
35 mm²125 A97 A46.77 V (20.34%)183.2 V77.16 V (33.55%)19879.1 WDrop High
50 mm²151 A118 A32.74 V (14.24%)197.3 V54.01 V (23.48%)13915.4 WDrop High
70 mm²192 A150 A23.39 V (10.17%)206.6 V38.58 V (16.77%)9939.5 WDrop High
95 mm²232 A181 A17.23 V (7.49%)212.8 V28.43 V (12.36%)7323.9 WDrop High
120 mm²269 A210 A13.64 V (5.93%)216.4 V22.5 V (9.78%)5798.1 WDrop High
150 mm²309 A241 A10.91 V (4.75%)219.1 V18.0 V (7.83%)4638.4 WDrop High
185 mm²353 A275 A8.85 V (3.85%)221.2 V14.6 V (6.35%)3760.9 WDrop High
240 mm²415 A324 A6.82 V (2.97%)223.2 V11.25 V (4.89%)2899.0 WDrop High
300 mm²477 A372 A5.46 V (2.37%)224.5 V9.0 V (3.91%)2319.2 W✓ OK (≤3%)
400 mm²570 A445 A4.09 V (1.78%)225.9 V6.75 V (2.94%)1739.4 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 90 Meter (230V)

Vilken kabelarea krävs för 425A vid 90 meter (230V)?

För 425 Ampere över 90 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (5.46V / 2.37%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.