Kabelarea för 450 Ampere vid 600 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 450 A över 600 m vid 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 8.34V (2.08%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 41.27V (10.32%)
Voltage at Load391.7 VLine Loss: 6500.2 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6671.86 V (1667.96%)0.0 V11005.45 V (2751.36%)5200200.0 WDrop High
2.5 mm²24 A18 A4003.12 V (1000.78%)0.0 V6603.27 V (1650.82%)3120120.0 WDrop High
4 mm²32 A25 A2501.95 V (625.49%)0.0 V4127.04 V (1031.76%)1950075.0 WDrop High
6 mm²41 A32 A1667.96 V (416.99%)0.0 V2751.36 V (687.84%)1300050.0 WDrop High
10 mm²57 A44 A1000.78 V (250.19%)0.0 V1650.82 V (412.7%)780030.0 WDrop High
16 mm²76 A59 A625.49 V (156.37%)0.0 V1031.76 V (257.94%)487518.8 WDrop High
25 mm²101 A78 A400.31 V (100.08%)0.0 V660.33 V (165.08%)312012.0 WDrop High
35 mm²125 A97 A285.94 V (71.48%)114.1 V471.66 V (117.92%)222865.7 WDrop High
50 mm²151 A118 A200.16 V (50.04%)199.8 V330.16 V (82.54%)156006.0 WDrop High
70 mm²192 A150 A142.97 V (35.74%)257.0 V235.83 V (58.96%)111432.9 WDrop High
95 mm²232 A181 A105.35 V (26.34%)294.7 V173.77 V (43.44%)82108.4 WDrop High
120 mm²269 A210 A83.4 V (20.85%)316.6 V137.57 V (34.39%)65002.5 WDrop High
150 mm²309 A241 A66.72 V (16.68%)333.3 V110.05 V (27.51%)52002.0 WDrop High
185 mm²353 A275 A54.1 V (13.52%)345.9 V89.23 V (22.31%)42163.8 WDrop High
240 mm²415 A324 A41.7 V (10.42%)358.3 V68.78 V (17.2%)32501.2 WDrop High
300 mm²477 A372 A33.36 V (8.34%)366.6 V55.03 V (13.76%)26001.0 WDrop High
400 mm²570 A445 A25.02 V (6.25%)375.0 V41.27 V (10.32%)19500.7 WDrop High

FAQ — Kabelarea för 450 Ampere vid 600 Meter (400V)

Vilken kabelarea krävs för 450A vid 600 meter (400V)?

För 450 Ampere över 600 meter vid 400V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (8.34V / 2.08%).

Hur stor effekt motsvarar 450A vid 400V?

Det motsvarar 311.77 kW med en rekommenderad säkring på 450A.