Kabelarea för 475 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 175 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 10.27V (2.57%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.71V (3.18%)
Voltage at Load389.7 VLine Loss: 8449.7 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2054.07 V (513.52%)0.0 V3388.25 V (847.06%)1689931.2 WDrop High
2.5 mm²24 A18 A1232.44 V (308.11%)0.0 V2032.95 V (508.24%)1013958.7 WDrop High
4 mm²32 A25 A770.28 V (192.57%)0.0 V1270.59 V (317.65%)633724.2 WDrop High
6 mm²41 A32 A513.52 V (128.38%)0.0 V847.06 V (211.77%)422482.8 WDrop High
10 mm²57 A44 A308.11 V (77.03%)91.9 V508.24 V (127.06%)253489.7 WDrop High
16 mm²76 A59 A192.57 V (48.14%)207.4 V317.65 V (79.41%)158431.1 WDrop High
25 mm²101 A78 A123.24 V (30.81%)276.8 V203.3 V (50.82%)101395.9 WDrop High
35 mm²125 A97 A88.03 V (22.01%)312.0 V145.21 V (36.3%)72425.6 WDrop High
50 mm²151 A118 A61.62 V (15.41%)338.4 V101.65 V (25.41%)50697.9 WDrop High
70 mm²192 A150 A44.02 V (11.0%)356.0 V72.61 V (18.15%)36212.8 WDrop High
95 mm²232 A181 A32.43 V (8.11%)367.6 V53.5 V (13.37%)26683.1 WDrop High
120 mm²269 A210 A25.68 V (6.42%)374.3 V42.35 V (10.59%)21124.1 WDrop High
150 mm²309 A241 A20.54 V (5.14%)379.5 V33.88 V (8.47%)16899.3 WDrop High
185 mm²353 A275 A16.65 V (4.16%)383.3 V27.47 V (6.87%)13702.1 WDrop High
240 mm²415 A324 A12.84 V (3.21%)387.2 V21.18 V (5.29%)10562.1 WDrop High
300 mm²477 A372 A10.27 V (2.57%)389.7 V16.94 V (4.24%)8449.7 W✓ OK (≤3%)
400 mm²570 A445 A7.7 V (1.93%)392.3 V12.71 V (3.18%)6337.2 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 475A vid 175 meter (400V)?

För 475 Ampere över 175 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (10.27V / 2.57%).

Hur stor effekt motsvarar 475A vid 400V?

Det motsvarar 329.09 kW med en rekommenderad säkring på 500A.