Kabelarea för 475 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 80 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 5.42V (2.36%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.71V (2.92%)
Voltage at Load224.6 VLine Loss: 2575.1 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1084.27 V (471.42%)0.0 V1788.53 V (777.62%)515026.7 WDrop High
2.5 mm²24 A18 A650.56 V (282.85%)0.0 V1073.12 V (466.57%)309016.0 WDrop High
4 mm²32 A25 A406.6 V (176.78%)0.0 V670.7 V (291.61%)193135.0 WDrop High
6 mm²41 A32 A271.07 V (117.86%)0.0 V447.13 V (194.41%)128756.7 WDrop High
10 mm²57 A44 A162.64 V (70.71%)67.4 V268.28 V (116.64%)77254.0 WDrop High
16 mm²76 A59 A101.65 V (44.2%)128.4 V167.67 V (72.9%)48283.8 WDrop High
25 mm²101 A78 A65.06 V (28.29%)164.9 V107.31 V (46.66%)30901.6 WDrop High
35 mm²125 A97 A46.47 V (20.2%)183.5 V76.65 V (33.33%)22072.6 WDrop High
50 mm²151 A118 A32.53 V (14.14%)197.5 V53.66 V (23.33%)15450.8 WDrop High
70 mm²192 A150 A23.23 V (10.1%)206.8 V38.33 V (16.66%)11036.3 WDrop High
95 mm²232 A181 A17.12 V (7.44%)212.9 V28.24 V (12.28%)8132.0 WDrop High
120 mm²269 A210 A13.55 V (5.89%)216.4 V22.36 V (9.72%)6437.8 WDrop High
150 mm²309 A241 A10.84 V (4.71%)219.2 V17.89 V (7.78%)5150.3 WDrop High
185 mm²353 A275 A8.79 V (3.82%)221.2 V14.5 V (6.31%)4175.9 WDrop High
240 mm²415 A324 A6.78 V (2.95%)223.2 V11.18 V (4.86%)3218.9 WDrop High
300 mm²477 A372 A5.42 V (2.36%)224.6 V8.94 V (3.89%)2575.1 W✓ OK (≤3%)
400 mm²570 A445 A4.07 V (1.77%)225.9 V6.71 V (2.92%)1931.3 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 475A vid 80 meter (230V)?

För 475 Ampere över 80 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (5.42V / 2.36%).

Hur stor effekt motsvarar 475A vid 230V?

Det motsvarar 109.25 kW med en rekommenderad säkring på 500A.