Kabelarea för 550 Ampere vid 500 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 550 A över 500 m vid 400V.

Copper Cable (≤3% Drop)3× 400 mm²Drop: 8.49V (2.12%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 42.03V (10.51%)
Voltage at Load391.5 VLine Loss: 8091.9 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6795.41 V (1698.85%)0.0 V11209.26 V (2802.31%)6473500.0 WDrop High
2.5 mm²24 A18 A4077.25 V (1019.31%)0.0 V6725.55 V (1681.39%)3884100.0 WDrop High
4 mm²32 A25 A2548.28 V (637.07%)0.0 V4203.47 V (1050.87%)2427562.5 WDrop High
6 mm²41 A32 A1698.85 V (424.71%)0.0 V2802.31 V (700.58%)1618375.0 WDrop High
10 mm²57 A44 A1019.31 V (254.83%)0.0 V1681.39 V (420.35%)971025.0 WDrop High
16 mm²76 A59 A637.07 V (159.27%)0.0 V1050.87 V (262.72%)606890.6 WDrop High
25 mm²101 A78 A407.72 V (101.93%)0.0 V672.56 V (168.14%)388410.0 WDrop High
35 mm²125 A97 A291.23 V (72.81%)108.8 V480.4 V (120.1%)277435.7 WDrop High
50 mm²151 A118 A203.86 V (50.97%)196.1 V336.28 V (84.07%)194205.0 WDrop High
70 mm²192 A150 A145.62 V (36.4%)254.4 V240.2 V (60.05%)138717.9 WDrop High
95 mm²232 A181 A107.3 V (26.82%)292.7 V176.99 V (44.25%)102213.2 WDrop High
120 mm²269 A210 A84.94 V (21.24%)315.1 V140.12 V (35.03%)80918.7 WDrop High
150 mm²309 A241 A67.95 V (16.99%)332.0 V112.09 V (28.02%)64735.0 WDrop High
185 mm²353 A275 A55.1 V (13.77%)344.9 V90.89 V (22.72%)52487.8 WDrop High
240 mm²415 A324 A42.47 V (10.62%)357.5 V70.06 V (17.51%)40459.4 WDrop High
300 mm²477 A372 A33.98 V (8.49%)366.0 V56.05 V (14.01%)32367.5 WDrop High
400 mm²570 A445 A25.48 V (6.37%)374.5 V42.03 V (10.51%)24275.6 WDrop High

FAQ — Kabelarea för 550 Ampere vid 500 Meter (400V)

Vilken kabelarea krävs för 550A vid 500 meter (400V)?

För 550 Ampere över 500 meter vid 400V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (8.49V / 2.12%).

Hur stor effekt motsvarar 550A vid 400V?

Det motsvarar 381.05 kW med en rekommenderad säkring på 600A.