Kabelarea för 800 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 800 A över 120 m vid 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.45V (1.11%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.67V (3.67%)
Voltage at Load395.6 VLine Loss: 6163.2 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2372.22 V (593.05%)0.0 V3913.05 V (978.26%)3287040.0 WDrop High
2.5 mm²24 A18 A1423.33 V (355.83%)0.0 V2347.83 V (586.96%)1972224.0 WDrop High
4 mm²32 A25 A889.58 V (222.4%)0.0 V1467.39 V (366.85%)1232640.0 WDrop High
6 mm²41 A32 A593.05 V (148.26%)0.0 V978.26 V (244.57%)821760.0 WDrop High
10 mm²57 A44 A355.83 V (88.96%)44.2 V586.96 V (146.74%)493056.0 WDrop High
16 mm²76 A59 A222.4 V (55.6%)177.6 V366.85 V (91.71%)308160.0 WDrop High
25 mm²101 A78 A142.33 V (35.58%)257.7 V234.78 V (58.7%)197222.4 WDrop High
35 mm²125 A97 A101.67 V (25.42%)298.3 V167.7 V (41.93%)140873.1 WDrop High
50 mm²151 A118 A71.17 V (17.79%)328.8 V117.39 V (29.35%)98611.2 WDrop High
70 mm²192 A150 A50.83 V (12.71%)349.2 V83.85 V (20.96%)70436.6 WDrop High
95 mm²232 A181 A37.46 V (9.36%)362.5 V61.78 V (15.45%)51900.6 WDrop High
120 mm²269 A210 A29.65 V (7.41%)370.3 V48.91 V (12.23%)41088.0 WDrop High
150 mm²309 A241 A23.72 V (5.93%)376.3 V39.13 V (9.78%)32870.4 WDrop High
185 mm²353 A275 A19.23 V (4.81%)380.8 V31.73 V (7.93%)26651.7 WDrop High
240 mm²415 A324 A14.83 V (3.71%)385.2 V24.46 V (6.11%)20544.0 WDrop High
300 mm²477 A372 A11.86 V (2.97%)388.1 V19.57 V (4.89%)16435.2 WDrop High
400 mm²570 A445 A8.9 V (2.22%)391.1 V14.67 V (3.67%)12326.4 WDrop High

FAQ — Kabelarea för 800 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 800A vid 120 meter (400V)?

För 800 Ampere över 120 meter vid 400V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.45V / 1.11%).

Hur stor effekt motsvarar 800A vid 400V?

Det motsvarar 554.26 kW med en rekommenderad säkring på 800A.