⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

10 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 10 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)6 AWGDrop: 14.01V (2.92%)
Voltage at Load End466.5 VLoss: 13.5 V (233.8 W)
Power & Breaker (125%)8.31 kW13A Breaker Recommended

All AWG & kcmil Wire Gauges for 10 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A54.32 V (11.32%)425.7 V89.6 V (18.67%)940.8 WDrop/Amp High
12 AWG3.31 mm²20 A34.13 V (7.11%)445.9 V56.3 V (11.73%)591.2 WDrop/Amp High
10 AWG5.26 mm²30 A21.48 V (4.47%)458.5 V35.43 V (7.38%)372.0 W~ ≤5%
8 AWG8.37 mm²50 A13.5 V (2.81%)466.5 V22.27 V (4.64%)233.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A8.49 V (1.77%)471.5 V14.01 V (2.92%)147.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A5.34 V (1.11%)474.7 V8.81 V (1.84%)92.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.24 V (0.88%)475.8 V6.99 V (1.46%)73.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.36 V (0.7%)476.6 V5.54 V (1.15%)58.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.66 V (0.55%)477.3 V4.39 V (0.92%)46.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.11 V (0.44%)477.9 V3.48 V (0.73%)36.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.68 V (0.35%)478.3 V2.76 V (0.58%)29.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.33 V (0.28%)478.7 V2.19 V (0.46%)23.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.05 V (0.22%)478.9 V1.74 V (0.36%)18.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.89 V (0.19%)479.1 V1.47 V (0.31%)15.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.74 V (0.15%)479.3 V1.23 V (0.26%)12.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.64 V (0.13%)479.4 V1.05 V (0.22%)11.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.56 V (0.12%)479.4 V0.92 V (0.19%)9.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.45 V (0.09%)479.6 V0.74 V (0.15%)7.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.37 V (0.08%)479.6 V0.61 V (0.13%)6.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.3 V (0.06%)479.7 V0.49 V (0.1%)5.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.22 V (0.05%)479.8 V0.37 V (0.08%)3.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 10 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 10A load over 1000 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 13.5V (2.81%) and delivers 466.5V at the load.

What size aluminum wire is required for 10 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 14.01V (2.92%).

What breaker size is needed for a 10A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (10A × 1.25 = 12.5A), which corresponds to a standard 13A circuit breaker.