🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.58%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.19V (1.92%)
Voltage at Load End477.2 VLoss: 2.79 V (4827.4 W)
Power & Breaker (125%)831.38 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1357.89 V (282.89%)0.0 V2239.89 V (466.64%)2351942.3 WDrop/Amp High
12 AWG3.31 mm²20 A853.3 V (177.77%)0.0 V1407.55 V (293.24%)1477957.7 WDrop/Amp High
10 AWG5.26 mm²30 A536.96 V (111.87%)0.0 V885.74 V (184.53%)930045.6 WDrop/Amp High
8 AWG8.37 mm²50 A337.45 V (70.3%)142.6 V556.63 V (115.96%)584473.1 WDrop/Amp High
6 AWG13.3 mm²65 A212.36 V (44.24%)267.6 V350.3 V (72.98%)367822.6 WDrop/Amp High
4 AWG21.15 mm²85 A133.54 V (27.82%)346.5 V220.28 V (45.89%)231302.1 WDrop/Amp High
3 AWG26.67 mm²100 A105.9 V (22.06%)374.1 V174.69 V (36.39%)183428.6 WDrop/Amp High
2 AWG33.62 mm²115 A84.01 V (17.5%)396.0 V138.58 V (28.87%)145509.8 WDrop/Amp High
1 AWG42.41 mm²130 A66.6 V (13.87%)413.4 V109.86 V (22.89%)115351.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A52.8 V (11.0%)427.2 V87.1 V (18.15%)91457.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A41.89 V (8.73%)438.1 V69.09 V (14.39%)72549.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.22 V (6.92%)446.8 V54.81 V (11.42%)57546.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.35 V (5.49%)453.7 V43.46 V (9.05%)45634.7 WDrop/Amp High
250 kcmil126.7 mm²255 A22.29 V (4.64%)457.7 V36.77 V (7.66%)38611.2 WDrop/Amp High
300 kcmil152.0 mm²285 A18.58 V (3.87%)461.4 V30.65 V (6.39%)32184.5 WDrop/Amp High
350 kcmil177.3 mm²310 A15.93 V (3.32%)464.1 V26.28 V (5.47%)27591.9 WDrop/Amp High
400 kcmil202.7 mm²335 A13.93 V (2.9%)466.1 V22.98 V (4.79%)24134.4 WDrop/Amp High
500 kcmil253.4 mm²380 A11.15 V (2.32%)468.9 V18.39 V (3.83%)19305.6 WDrop/Amp High
600 kcmil304.0 mm²420 A9.29 V (1.94%)470.7 V15.33 V (3.19%)16092.2 WDrop/Amp High
750 kcmil380.0 mm²475 A7.43 V (1.55%)472.6 V12.26 V (2.55%)12873.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.57 V (1.16%)474.4 V9.19 V (1.92%)9654.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 250 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.79V (0.58%) and delivers 477.2V at the load.

What size aluminum wire is required for 1000 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.19V (1.92%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.