🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

1000 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 1000 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.48%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 29.42V (12.26%)
Voltage at Load End234.1 VLoss: 5.95 V (10298.4 W)
Power & Breaker (125%)415.69 kW1600A Breaker Recommended

All AWG & kcmil Wire Gauges for 1000 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4345.26 V (1810.53%)0.0 V7167.65 V (2986.52%)7526215.4 WDrop/Amp High
12 AWG3.31 mm²20 A2730.56 V (1137.73%)0.0 V4504.14 V (1876.73%)4729464.7 WDrop/Amp High
10 AWG5.26 mm²30 A1718.28 V (715.95%)0.0 V2834.36 V (1180.98%)2976146.0 WDrop/Amp High
8 AWG8.37 mm²50 A1079.83 V (449.93%)0.0 V1781.21 V (742.17%)1870314.0 WDrop/Amp High
6 AWG13.3 mm²65 A679.56 V (283.15%)0.0 V1120.96 V (467.07%)1177032.2 WDrop/Amp High
4 AWG21.15 mm²85 A427.34 V (178.06%)0.0 V704.9 V (293.71%)740166.8 WDrop/Amp High
3 AWG26.67 mm²100 A338.89 V (141.2%)0.0 V559.01 V (232.92%)586971.4 WDrop/Amp High
2 AWG33.62 mm²115 A268.83 V (112.01%)0.0 V443.45 V (184.77%)465631.4 WDrop/Amp High
1 AWG42.41 mm²130 A213.11 V (88.8%)26.9 V351.54 V (146.47%)369123.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A168.97 V (70.4%)71.0 V278.72 V (116.13%)292662.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A134.04 V (55.85%)106.0 V221.1 V (92.12%)232159.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A106.32 V (44.3%)133.7 V175.38 V (73.07%)184149.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A84.31 V (35.13%)155.7 V139.07 V (57.95%)146031.0 WDrop/Amp High
250 kcmil126.7 mm²255 A71.34 V (29.72%)168.7 V117.67 V (49.03%)123555.9 WDrop/Amp High
300 kcmil152.0 mm²285 A59.46 V (24.78%)180.5 V98.08 V (40.87%)102990.3 WDrop/Amp High
350 kcmil177.3 mm²310 A50.98 V (21.24%)189.0 V84.09 V (35.04%)88294.0 WDrop/Amp High
400 kcmil202.7 mm²335 A44.59 V (18.58%)195.4 V73.55 V (30.65%)77230.0 WDrop/Amp High
500 kcmil253.4 mm²380 A35.67 V (14.86%)204.3 V58.83 V (24.51%)61777.9 WDrop/Amp High
600 kcmil304.0 mm²420 A29.73 V (12.39%)210.3 V49.04 V (20.43%)51495.2 WDrop/Amp High
750 kcmil380.0 mm²475 A23.78 V (9.91%)216.2 V39.23 V (16.35%)41196.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A17.84 V (7.43%)222.2 V29.42 V (12.26%)30895.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 1000 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 1000A load over 800 feet one-way at 240V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.95V (2.48%) and delivers 234.1V at the load.

What size aluminum wire is required for 1000 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 29.42V (12.26%).

What breaker size is needed for a 1000A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (1000A × 1.25 = 1250.0A), which corresponds to a standard 1600A circuit breaker.