🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 1.35%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 6.71V (1.4%)
Voltage at Load End473.5 VLoss: 6.47 V (1232.5 W)
Power & Breaker (125%)91.45 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A104.56 V (21.78%)375.4 V172.47 V (35.93%)19921.0 WDrop/Amp High
12 AWG3.31 mm²20 A65.7 V (13.69%)414.3 V108.38 V (22.58%)12518.3 WDrop/Amp High
10 AWG5.26 mm²30 A41.35 V (8.61%)438.7 V68.2 V (14.21%)7877.5 WDrop/Amp High
8 AWG8.37 mm²50 A25.98 V (5.41%)454.0 V42.86 V (8.93%)4950.5 WDrop/Amp High
6 AWG13.3 mm²65 A16.35 V (3.41%)463.6 V26.97 V (5.62%)3115.5 WDrop/Amp High
4 AWG21.15 mm²85 A10.28 V (2.14%)469.7 V16.96 V (3.53%)1959.1 WDrop/Amp High
3 AWG26.67 mm²100 A8.15 V (1.7%)471.8 V13.45 V (2.8%)1553.6 WDrop/Amp High
2 AWG33.62 mm²115 A6.47 V (1.35%)473.5 V10.67 V (2.22%)1232.5 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A5.13 V (1.07%)474.9 V8.46 V (1.76%)977.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.07 V (0.85%)475.9 V6.71 V (1.4%)774.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.23 V (0.67%)476.8 V5.32 V (1.11%)614.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.56 V (0.53%)477.4 V4.22 V (0.88%)487.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.03 V (0.42%)478.0 V3.35 V (0.7%)386.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.72 V (0.36%)478.3 V2.83 V (0.59%)327.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.43 V (0.3%)478.6 V2.36 V (0.49%)272.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.23 V (0.26%)478.8 V2.02 V (0.42%)233.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.07 V (0.22%)478.9 V1.77 V (0.37%)204.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.86 V (0.18%)479.1 V1.42 V (0.29%)163.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.72 V (0.15%)479.3 V1.18 V (0.25%)136.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.57 V (0.12%)479.4 V0.94 V (0.2%)109.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.43 V (0.09%)479.6 V0.71 V (0.15%)81.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 175 feet one-way at 480V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 6.47V (1.35%) and delivers 473.5V at the load.

What size aluminum wire is required for 110 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 6.71V (1.4%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.