🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 0.96%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 4.79V (1.0%)
Voltage at Load End475.4 VLoss: 4.62 V (880.3 W)
Power & Breaker (125%)91.45 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A74.68 V (15.56%)405.3 V123.19 V (25.67%)14229.3 WDrop/Amp High
12 AWG3.31 mm²20 A46.93 V (9.78%)433.1 V77.41 V (16.13%)8941.6 WDrop/Amp High
10 AWG5.26 mm²30 A29.53 V (6.15%)450.5 V48.72 V (10.15%)5626.8 WDrop/Amp High
8 AWG8.37 mm²50 A18.56 V (3.87%)461.4 V30.61 V (6.38%)3536.1 WDrop/Amp High
6 AWG13.3 mm²65 A11.68 V (2.43%)468.3 V19.27 V (4.01%)2225.3 WDrop/Amp High
4 AWG21.15 mm²85 A7.34 V (1.53%)472.7 V12.12 V (2.52%)1399.4 WDrop/Amp High
3 AWG26.67 mm²100 A5.82 V (1.21%)474.2 V9.61 V (2.0%)1109.7 WDrop/Amp High
2 AWG33.62 mm²115 A4.62 V (0.96%)475.4 V7.62 V (1.59%)880.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.66 V (0.76%)476.3 V6.04 V (1.26%)697.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.9 V (0.61%)477.1 V4.79 V (1.0%)553.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.3 V (0.48%)477.7 V3.8 V (0.79%)438.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.83 V (0.38%)478.2 V3.01 V (0.63%)348.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.45 V (0.3%)478.6 V2.39 V (0.5%)276.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.23 V (0.26%)478.8 V2.02 V (0.42%)233.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.02 V (0.21%)479.0 V1.69 V (0.35%)194.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.88 V (0.18%)479.1 V1.45 V (0.3%)166.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.77 V (0.16%)479.2 V1.26 V (0.26%)146.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.61 V (0.13%)479.4 V1.01 V (0.21%)116.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.51 V (0.11%)479.5 V0.84 V (0.18%)97.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.41 V (0.09%)479.6 V0.67 V (0.14%)77.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.31 V (0.06%)479.7 V0.51 V (0.11%)58.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 125 feet one-way at 480V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 4.62V (0.96%) and delivers 475.4V at the load.

What size aluminum wire is required for 110 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 4.79V (1.0%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.