🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 400 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 6.23V (2.6%)
Voltage at Load End233.2 VLoss: 6.75 V (742.7 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A275.96 V (114.98%)0.0 V455.21 V (189.67%)30355.7 WDrop/Amp High
12 AWG3.31 mm²20 A173.41 V (72.26%)66.6 V286.05 V (119.19%)19075.5 WDrop/Amp High
10 AWG5.26 mm²30 A109.13 V (45.47%)130.9 V180.01 V (75.0%)12003.8 WDrop/Amp High
8 AWG8.37 mm²50 A68.58 V (28.57%)171.4 V113.12 V (47.13%)7543.6 WDrop/Amp High
6 AWG13.3 mm²65 A43.16 V (17.98%)196.8 V71.19 V (29.66%)4747.4 WDrop/Amp High
4 AWG21.15 mm²85 A27.14 V (11.31%)212.9 V44.77 V (18.65%)2985.3 WDrop/Amp High
3 AWG26.67 mm²100 A21.52 V (8.97%)218.5 V35.5 V (14.79%)2367.5 WDrop/Amp High
2 AWG33.62 mm²115 A17.07 V (7.11%)222.9 V28.16 V (11.73%)1878.0 WDrop/Amp High
1 AWG42.41 mm²130 A13.53 V (5.64%)226.5 V22.33 V (9.3%)1488.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.73 V (4.47%)229.3 V17.7 V (7.38%)1180.4 W~ ≤5%
2/0 AWG67.43 mm²175 A8.51 V (3.55%)231.5 V14.04 V (5.85%)936.4 W~ ≤5%
3/0 AWG85.01 mm²200 A6.75 V (2.81%)233.2 V11.14 V (4.64%)742.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.35 V (2.23%)234.6 V8.83 V (3.68%)589.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.53 V (1.89%)235.5 V7.47 V (3.11%)498.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.78 V (1.57%)236.2 V6.23 V (2.6%)415.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.24 V (1.35%)236.8 V5.34 V (2.23%)356.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.83 V (1.18%)237.2 V4.67 V (1.95%)311.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.27 V (0.94%)237.7 V3.74 V (1.56%)249.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.89 V (0.79%)238.1 V3.11 V (1.3%)207.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.51 V (0.63%)238.5 V2.49 V (1.04%)166.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.13 V (0.47%)238.9 V1.87 V (0.78%)124.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 400 feet one-way at 240V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 6.75V (2.81%) and delivers 233.2V at the load.

What size aluminum wire is required for 110 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 6.23V (2.6%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.