🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 6.94V (2.89%)
Voltage at Load End233.0 VLoss: 6.96 V (1325.2 W)
Power & Breaker (125%)45.73 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A358.48 V (149.37%)0.0 V591.33 V (246.39%)68300.4 WDrop/Amp High
12 AWG3.31 mm²20 A225.27 V (93.86%)14.7 V371.59 V (154.83%)42919.9 WDrop/Amp High
10 AWG5.26 mm²30 A141.76 V (59.07%)98.2 V233.83 V (97.43%)27008.5 WDrop/Amp High
8 AWG8.37 mm²50 A89.09 V (37.12%)150.9 V146.95 V (61.23%)16973.1 WDrop/Amp High
6 AWG13.3 mm²65 A56.06 V (23.36%)183.9 V92.48 V (38.53%)10681.6 WDrop/Amp High
4 AWG21.15 mm²85 A35.26 V (14.69%)204.7 V58.15 V (24.23%)6717.0 WDrop/Amp High
3 AWG26.67 mm²100 A27.96 V (11.65%)212.0 V46.12 V (19.22%)5326.8 WDrop/Amp High
2 AWG33.62 mm²115 A22.18 V (9.24%)217.8 V36.58 V (15.24%)4225.6 WDrop/Amp High
1 AWG42.41 mm²130 A17.58 V (7.33%)222.4 V29.0 V (12.08%)3349.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.94 V (5.81%)226.1 V22.99 V (9.58%)2655.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.06 V (4.61%)228.9 V18.24 V (7.6%)2106.8 W~ ≤5%
3/0 AWG85.01 mm²200 A8.77 V (3.65%)231.2 V14.47 V (6.03%)1671.2 W~ ≤5%
4/0 AWG107.2 mm²230 A6.96 V (2.9%)233.0 V11.47 V (4.78%)1325.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A5.89 V (2.45%)234.1 V9.71 V (4.04%)1121.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.91 V (2.04%)235.1 V8.09 V (3.37%)934.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.21 V (1.75%)235.8 V6.94 V (2.89%)801.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.68 V (1.53%)236.3 V6.07 V (2.53%)700.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.94 V (1.23%)237.1 V4.85 V (2.02%)560.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.45 V (1.02%)237.5 V4.05 V (1.69%)467.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.96 V (0.82%)238.0 V3.24 V (1.35%)373.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.47 V (0.61%)238.5 V2.43 V (1.01%)280.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 600 feet one-way at 240V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 6.96V (2.9%) and delivers 233.0V at the load.

What size aluminum wire is required for 110 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 6.94V (2.89%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.