🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 6.07V (2.53%)
Voltage at Load End233.9 VLoss: 6.13 V (1168.3 W)
Power & Breaker (125%)45.73 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A448.11 V (186.71%)0.0 V739.16 V (307.99%)85375.5 WDrop/Amp High
12 AWG3.31 mm²20 A281.59 V (117.33%)0.0 V464.49 V (193.54%)53649.9 WDrop/Amp High
10 AWG5.26 mm²30 A177.2 V (73.83%)62.8 V292.29 V (121.79%)33760.7 WDrop/Amp High
8 AWG8.37 mm²50 A111.36 V (46.4%)128.6 V183.69 V (76.54%)21216.4 WDrop/Amp High
6 AWG13.3 mm²65 A70.08 V (29.2%)169.9 V115.6 V (48.17%)13352.0 WDrop/Amp High
4 AWG21.15 mm²85 A44.07 V (18.36%)195.9 V72.69 V (30.29%)8396.3 WDrop/Amp High
3 AWG26.67 mm²100 A34.95 V (14.56%)205.1 V57.65 V (24.02%)6658.5 WDrop/Amp High
2 AWG33.62 mm²115 A27.72 V (11.55%)212.3 V45.73 V (19.05%)5282.0 WDrop/Amp High
1 AWG42.41 mm²130 A21.98 V (9.16%)218.0 V36.25 V (15.11%)4187.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.42 V (7.26%)222.6 V28.74 V (11.98%)3319.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.82 V (5.76%)226.2 V22.8 V (9.5%)2633.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.96 V (4.57%)229.0 V18.09 V (7.54%)2088.9 W~ ≤5%
4/0 AWG107.2 mm²230 A8.69 V (3.62%)231.3 V14.34 V (5.98%)1656.5 W~ ≤5%
250 kcmil126.7 mm²255 A7.36 V (3.07%)232.6 V12.13 V (5.06%)1401.6 W~ ≤5%
300 kcmil152.0 mm²285 A6.13 V (2.55%)233.9 V10.11 V (4.21%)1168.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.26 V (2.19%)234.7 V8.67 V (3.61%)1001.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.6 V (1.92%)235.4 V7.58 V (3.16%)876.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.68 V (1.53%)236.3 V6.07 V (2.53%)700.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.07 V (1.28%)236.9 V5.06 V (2.11%)584.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.45 V (1.02%)237.5 V4.05 V (1.69%)467.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.84 V (0.77%)238.2 V3.03 V (1.26%)350.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 750 feet one-way at 240V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 6.13V (2.55%) and delivers 233.9V at the load.

What size aluminum wire is required for 110 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 6.07V (2.53%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.