🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 1000 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.71%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.44V (2.68%)
Voltage at Load End233.5 VLoss: 6.5 V (1971.3 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A950.53 V (396.05%)0.0 V1567.92 V (653.3%)288112.9 WDrop/Amp High
12 AWG3.31 mm²20 A597.31 V (248.88%)0.0 V985.28 V (410.53%)181049.8 WDrop/Amp High
10 AWG5.26 mm²30 A375.87 V (156.61%)0.0 V620.02 V (258.34%)113930.6 WDrop/Amp High
8 AWG8.37 mm²50 A236.21 V (98.42%)3.8 V389.64 V (162.35%)71598.0 WDrop/Amp High
6 AWG13.3 mm²65 A148.65 V (61.94%)91.3 V245.21 V (102.17%)45058.3 WDrop/Amp High
4 AWG21.15 mm²85 A93.48 V (38.95%)146.5 V154.2 V (64.25%)28334.5 WDrop/Amp High
3 AWG26.67 mm²100 A74.13 V (30.89%)165.9 V122.28 V (50.95%)22470.0 WDrop/Amp High
2 AWG33.62 mm²115 A58.81 V (24.5%)181.2 V97.0 V (40.42%)17825.0 WDrop/Amp High
1 AWG42.41 mm²130 A46.62 V (19.42%)193.4 V76.9 V (32.04%)14130.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.96 V (15.4%)203.0 V60.97 V (25.4%)11203.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.32 V (12.22%)210.7 V48.37 V (20.15%)8887.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.26 V (9.69%)216.7 V38.36 V (15.98%)7049.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.44 V (7.68%)221.6 V30.42 V (12.68%)5590.3 WDrop/Amp High
250 kcmil126.7 mm²255 A15.6 V (6.5%)224.4 V25.74 V (10.73%)4729.9 WDrop/Amp High
300 kcmil152.0 mm²285 A13.01 V (5.42%)227.0 V21.46 V (8.94%)3942.6 WDrop/Amp High
350 kcmil177.3 mm²310 A11.15 V (4.65%)228.8 V18.39 V (7.66%)3380.0 W~ ≤5%
400 kcmil202.7 mm²335 A9.75 V (4.06%)230.2 V16.09 V (6.7%)2956.5 W~ ≤5%
500 kcmil253.4 mm²380 A7.8 V (3.25%)232.2 V12.87 V (5.36%)2364.9 W~ ≤5%
600 kcmil304.0 mm²420 A6.5 V (2.71%)233.5 V10.73 V (4.47%)1971.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A5.2 V (2.17%)234.8 V8.58 V (3.58%)1577.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.9 V (1.63%)236.1 V6.44 V (2.68%)1182.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 1000 feet one-way at 240V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 6.5V (2.71%) and delivers 233.5V at the load.

What size aluminum wire is required for 175 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.44V (2.68%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.