🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.69%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 6.44V (2.68%)
Voltage at Load End233.5 VLoss: 6.46 V (1956.6 W)
Power & Breaker (125%)72.75 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A332.68 V (138.62%)0.0 V548.77 V (228.66%)100839.5 WDrop/Amp High
12 AWG3.31 mm²20 A209.06 V (87.11%)30.9 V344.85 V (143.69%)63367.4 WDrop/Amp High
10 AWG5.26 mm²30 A131.56 V (54.81%)108.4 V217.01 V (90.42%)39875.7 WDrop/Amp High
8 AWG8.37 mm²50 A82.67 V (34.45%)157.3 V136.37 V (56.82%)25059.3 WDrop/Amp High
6 AWG13.3 mm²65 A52.03 V (21.68%)188.0 V85.82 V (35.76%)15770.4 WDrop/Amp High
4 AWG21.15 mm²85 A32.72 V (13.63%)207.3 V53.97 V (22.49%)9917.1 WDrop/Amp High
3 AWG26.67 mm²100 A25.95 V (10.81%)214.1 V42.8 V (17.83%)7864.5 WDrop/Amp High
2 AWG33.62 mm²115 A20.58 V (8.58%)219.4 V33.95 V (14.15%)6238.7 WDrop/Amp High
1 AWG42.41 mm²130 A16.32 V (6.8%)223.7 V26.91 V (11.21%)4945.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.94 V (5.39%)227.1 V21.34 V (8.89%)3921.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.26 V (4.28%)229.7 V16.93 V (7.05%)3110.6 W~ ≤5%
3/0 AWG85.01 mm²200 A8.14 V (3.39%)231.9 V13.43 V (5.59%)2467.3 W~ ≤5%
4/0 AWG107.2 mm²230 A6.46 V (2.69%)233.5 V10.65 V (4.44%)1956.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A5.46 V (2.28%)234.5 V9.01 V (3.75%)1655.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.55 V (1.9%)235.4 V7.51 V (3.13%)1379.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.9 V (1.63%)236.1 V6.44 V (2.68%)1183.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.41 V (1.42%)236.6 V5.63 V (2.35%)1034.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.73 V (1.14%)237.3 V4.5 V (1.88%)827.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.28 V (0.95%)237.7 V3.75 V (1.56%)690.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.82 V (0.76%)238.2 V3.0 V (1.25%)552.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.37 V (0.57%)238.6 V2.25 V (0.94%)413.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 350 feet one-way at 240V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 6.46V (2.69%) and delivers 233.5V at the load.

What size aluminum wire is required for 175 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 6.44V (2.68%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.