🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

175 Amp Wire Size at 600 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 175 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)8× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.46V (37.16%)
Voltage at Load End11.7 VLoss: 0.34 V (59.1 W)
Power & Breaker (125%)2.1 kW225A Breaker Recommended

All AWG & kcmil Wire Gauges for 175 Amps at 600 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A658.54 V (5487.87%)0.0 V1086.29 V (9052.41%)115245.2 WDrop/Amp High
12 AWG3.31 mm²20 A413.83 V (3448.57%)0.0 V682.62 V (5688.53%)72419.9 WDrop/Amp High
10 AWG5.26 mm²30 A260.41 V (2170.11%)0.0 V429.56 V (3579.66%)45572.2 WDrop/Amp High
8 AWG8.37 mm²50 A163.65 V (1363.77%)0.0 V269.95 V (2249.58%)28639.2 WDrop/Amp High
6 AWG13.3 mm²65 A102.99 V (858.25%)0.0 V169.89 V (1415.72%)18023.3 WDrop/Amp High
4 AWG21.15 mm²85 A64.76 V (539.7%)0.0 V106.83 V (890.26%)11333.8 WDrop/Amp High
3 AWG26.67 mm²100 A51.36 V (428.0%)0.0 V84.72 V (706.0%)8988.0 WDrop/Amp High
2 AWG33.62 mm²115 A40.74 V (339.52%)0.0 V67.21 V (560.05%)7130.0 WDrop/Amp High
1 AWG42.41 mm²130 A32.3 V (269.15%)0.0 V53.28 V (443.98%)5652.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.61 V (213.4%)0.0 V42.24 V (352.01%)4481.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.31 V (169.28%)0.0 V33.51 V (279.24%)3554.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.11 V (134.28%)0.0 V26.58 V (221.49%)2819.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.78 V (106.48%)0.0 V21.08 V (175.64%)2236.1 WDrop/Amp High
250 kcmil126.7 mm²255 A10.81 V (90.09%)1.2 V17.83 V (148.61%)1891.9 WDrop/Amp High
300 kcmil152.0 mm²285 A9.01 V (75.1%)3.0 V14.87 V (123.88%)1577.0 WDrop/Amp High
350 kcmil177.3 mm²310 A7.73 V (64.38%)4.3 V12.74 V (106.2%)1352.0 WDrop/Amp High
400 kcmil202.7 mm²335 A6.76 V (56.31%)5.2 V11.15 V (92.89%)1182.6 WDrop/Amp High
500 kcmil253.4 mm²380 A5.41 V (45.05%)6.6 V8.92 V (74.31%)946.0 WDrop/Amp High
600 kcmil304.0 mm²420 A4.51 V (37.55%)7.5 V7.43 V (61.94%)788.5 WDrop/Amp High
750 kcmil380.0 mm²475 A3.6 V (30.04%)8.4 V5.95 V (49.55%)630.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.7 V (22.53%)9.3 V4.46 V (37.16%)473.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 175 amps at 600 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 175A load over 600 feet one-way at 12V (DC), you need 8× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.82%) and delivers 11.7V at the load.

What size aluminum wire is required for 175 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.46V (37.16%).

What breaker size is needed for a 175A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (175A × 1.25 = 218.8A), which corresponds to a standard 225A circuit breaker.