⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

20 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 20 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)4 AWGDrop: 14.1V (2.94%)
Voltage at Load End466.4 VLoss: 13.59 V (470.8 W)
Power & Breaker (125%)16.63 kW25A Breaker Recommended

All AWG & kcmil Wire Gauges for 20 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A86.91 V (18.11%)393.1 V143.35 V (29.87%)3010.5 WDrop/Amp High
12 AWG3.31 mm²20 A54.61 V (11.38%)425.4 V90.08 V (18.77%)1891.8 WDrop/Amp High
10 AWG5.26 mm²30 A34.37 V (7.16%)445.6 V56.69 V (11.81%)1190.5 WDrop/Amp High
8 AWG8.37 mm²50 A21.6 V (4.5%)458.4 V35.62 V (7.42%)748.1 W~ ≤5%
6 AWG13.3 mm²65 A13.59 V (2.83%)466.4 V22.42 V (4.67%)470.8 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A8.55 V (1.78%)471.5 V14.1 V (2.94%)296.1 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A6.78 V (1.41%)473.2 V11.18 V (2.33%)234.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A5.38 V (1.12%)474.6 V8.87 V (1.85%)186.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.26 V (0.89%)475.7 V7.03 V (1.46%)147.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.38 V (0.7%)476.6 V5.57 V (1.16%)117.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.68 V (0.56%)477.3 V4.42 V (0.92%)92.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.13 V (0.44%)477.9 V3.51 V (0.73%)73.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.69 V (0.35%)478.3 V2.78 V (0.58%)58.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.43 V (0.3%)478.6 V2.35 V (0.49%)49.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.19 V (0.25%)478.8 V1.96 V (0.41%)41.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.02 V (0.21%)479.0 V1.68 V (0.35%)35.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.89 V (0.19%)479.1 V1.47 V (0.31%)30.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.71 V (0.15%)479.3 V1.18 V (0.25%)24.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.59 V (0.12%)479.4 V0.98 V (0.2%)20.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.48 V (0.1%)479.5 V0.78 V (0.16%)16.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.36 V (0.07%)479.6 V0.59 V (0.12%)12.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 20 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 20A load over 800 feet one-way at 480V (3-Phase), you need 6 AWG copper wire. This produces a voltage drop of 13.59V (2.83%) and delivers 466.4V at the load.

What size aluminum wire is required for 20 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 14.1V (2.94%).

What breaker size is needed for a 20A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (20A × 1.25 = 25.0A), which corresponds to a standard 25A circuit breaker.