⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.82%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 14.03V (2.92%)
Voltage at Load End466.5 VLoss: 13.52 V (1873.0 W)
Power & Breaker (125%)66.51 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A347.62 V (72.42%)132.4 V573.41 V (119.46%)48167.8 WDrop/Amp High
12 AWG3.31 mm²20 A218.44 V (45.51%)261.6 V360.33 V (75.07%)30268.6 WDrop/Amp High
10 AWG5.26 mm²30 A137.46 V (28.64%)342.5 V226.75 V (47.24%)19047.3 WDrop/Amp High
8 AWG8.37 mm²50 A86.39 V (18.0%)393.6 V142.5 V (29.69%)11970.0 WDrop/Amp High
6 AWG13.3 mm²65 A54.36 V (11.33%)425.6 V89.68 V (18.68%)7533.0 WDrop/Amp High
4 AWG21.15 mm²85 A34.19 V (7.12%)445.8 V56.39 V (11.75%)4737.1 WDrop/Amp High
3 AWG26.67 mm²100 A27.11 V (5.65%)452.9 V44.72 V (9.32%)3756.6 WDrop/Amp High
2 AWG33.62 mm²115 A21.51 V (4.48%)458.5 V35.48 V (7.39%)2980.0 W~ ≤5%
1 AWG42.41 mm²130 A17.05 V (3.55%)463.0 V28.12 V (5.86%)2362.4 W~ ≤5%
1/0 AWG53.49 mm²150 A13.52 V (2.82%)466.5 V22.3 V (4.65%)1873.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A10.72 V (2.23%)469.3 V17.69 V (3.68%)1485.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A8.51 V (1.77%)471.5 V14.03 V (2.92%)1178.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A6.74 V (1.41%)473.3 V11.13 V (2.32%)934.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A5.71 V (1.19%)474.3 V9.41 V (1.96%)790.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.76 V (0.99%)475.2 V7.85 V (1.63%)659.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.08 V (0.85%)475.9 V6.73 V (1.4%)565.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.57 V (0.74%)476.4 V5.88 V (1.23%)494.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.85 V (0.59%)477.1 V4.71 V (0.98%)395.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.38 V (0.5%)477.6 V3.92 V (0.82%)329.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.9 V (0.4%)478.1 V3.14 V (0.65%)263.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.43 V (0.3%)478.6 V2.35 V (0.49%)197.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 800 feet one-way at 480V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 13.52V (2.82%) and delivers 466.5V at the load.

What size aluminum wire is required for 80 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 14.03V (2.92%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.