🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

400 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 400 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.48%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.77V (2.45%)
Voltage at Load End468.1 VLoss: 11.89 V (8239.2 W)
Power & Breaker (125%)332.55 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 400 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1738.1 V (362.11%)0.0 V2867.06 V (597.3%)1204194.5 WDrop/Amp High
12 AWG3.31 mm²20 A1092.22 V (227.55%)0.0 V1801.66 V (375.35%)756714.3 WDrop/Amp High
10 AWG5.26 mm²30 A687.31 V (143.19%)0.0 V1133.74 V (236.2%)476183.4 WDrop/Amp High
8 AWG8.37 mm²50 A431.93 V (89.99%)48.1 V712.48 V (148.43%)299250.2 WDrop/Amp High
6 AWG13.3 mm²65 A271.82 V (56.63%)208.2 V448.38 V (93.41%)188325.1 WDrop/Amp High
4 AWG21.15 mm²85 A170.93 V (35.61%)309.1 V281.96 V (58.74%)118426.7 WDrop/Amp High
3 AWG26.67 mm²100 A135.56 V (28.24%)344.4 V223.6 V (46.58%)93915.4 WDrop/Amp High
2 AWG33.62 mm²115 A107.53 V (22.4%)372.5 V177.38 V (36.95%)74501.0 WDrop/Amp High
1 AWG42.41 mm²130 A85.25 V (17.76%)394.8 V140.62 V (29.29%)59059.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A67.59 V (14.08%)412.4 V111.49 V (23.23%)46826.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A53.61 V (11.17%)426.4 V88.44 V (18.42%)37145.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A42.53 V (8.86%)437.5 V70.15 V (14.61%)29463.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A33.72 V (7.03%)446.3 V55.63 V (11.59%)23365.0 WDrop/Amp High
250 kcmil126.7 mm²255 A28.53 V (5.94%)451.5 V47.07 V (9.81%)19768.9 WDrop/Amp High
300 kcmil152.0 mm²285 A23.78 V (4.96%)456.2 V39.23 V (8.17%)16478.5 WDrop/Amp High
350 kcmil177.3 mm²310 A20.39 V (4.25%)459.6 V33.64 V (7.01%)14127.0 WDrop/Amp High
400 kcmil202.7 mm²335 A17.84 V (3.72%)462.2 V29.42 V (6.13%)12356.8 WDrop/Amp High
500 kcmil253.4 mm²380 A14.27 V (2.97%)465.7 V23.53 V (4.9%)9884.5 WDrop/Amp High
600 kcmil304.0 mm²420 A11.89 V (2.48%)468.1 V19.62 V (4.09%)8239.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A9.51 V (1.98%)470.5 V15.69 V (3.27%)6591.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A7.13 V (1.49%)472.9 V11.77 V (2.45%)4943.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 400 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 400A load over 800 feet one-way at 480V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 11.89V (2.48%) and delivers 468.1V at the load.

What size aluminum wire is required for 400 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.77V (2.45%).

What breaker size is needed for a 400A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (400A × 1.25 = 500.0A), which corresponds to a standard 500A circuit breaker.