🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.77%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 12.26V (2.55%)
Voltage at Load End466.7 VLoss: 13.29 V (2877.3 W)
Power & Breaker (125%)103.92 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A543.16 V (113.16%)0.0 V895.96 V (186.66%)117597.1 WDrop/Amp High
12 AWG3.31 mm²20 A341.32 V (71.11%)138.7 V563.02 V (117.3%)73897.9 WDrop/Amp High
10 AWG5.26 mm²30 A214.78 V (44.75%)265.2 V354.29 V (73.81%)46502.3 WDrop/Amp High
8 AWG8.37 mm²50 A134.98 V (28.12%)345.0 V222.65 V (46.39%)29223.7 WDrop/Amp High
6 AWG13.3 mm²65 A84.94 V (17.7%)395.1 V140.12 V (29.19%)18391.1 WDrop/Amp High
4 AWG21.15 mm²85 A53.42 V (11.13%)426.6 V88.11 V (18.36%)11565.1 WDrop/Amp High
3 AWG26.67 mm²100 A42.36 V (8.83%)437.6 V69.88 V (14.56%)9171.4 WDrop/Amp High
2 AWG33.62 mm²115 A33.6 V (7.0%)446.4 V55.43 V (11.55%)7275.5 WDrop/Amp High
1 AWG42.41 mm²130 A26.64 V (5.55%)453.4 V43.94 V (9.15%)5767.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.12 V (4.4%)458.9 V34.84 V (7.26%)4572.9 W~ ≤5%
2/0 AWG67.43 mm²175 A16.75 V (3.49%)463.2 V27.64 V (5.76%)3627.5 W~ ≤5%
3/0 AWG85.01 mm²200 A13.29 V (2.77%)466.7 V21.92 V (4.57%)2877.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A10.54 V (2.2%)469.5 V17.38 V (3.62%)2281.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A8.92 V (1.86%)471.1 V14.71 V (3.06%)1930.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A7.43 V (1.55%)472.6 V12.26 V (2.55%)1609.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A6.37 V (1.33%)473.6 V10.51 V (2.19%)1379.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A5.57 V (1.16%)474.4 V9.19 V (1.92%)1206.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.46 V (0.93%)475.5 V7.35 V (1.53%)965.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.72 V (0.77%)476.3 V6.13 V (1.28%)804.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.97 V (0.62%)477.0 V4.9 V (1.02%)643.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.23 V (0.46%)477.8 V3.68 V (0.77%)482.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 800 feet one-way at 480V (3-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 13.29V (2.77%) and delivers 466.7V at the load.

What size aluminum wire is required for 125 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 12.26V (2.55%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.