🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 800 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.66%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 13.27V (2.76%)
Voltage at Load End467.2 VLoss: 12.79 V (1328.8 W)
Power & Breaker (125%)49.88 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 800 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A260.72 V (54.32%)219.3 V430.06 V (89.6%)27094.4 WDrop/Amp High
12 AWG3.31 mm²20 A163.83 V (34.13%)316.2 V270.25 V (56.3%)17026.1 WDrop/Amp High
10 AWG5.26 mm²30 A103.1 V (21.48%)376.9 V170.06 V (35.43%)10714.1 WDrop/Amp High
8 AWG8.37 mm²50 A64.79 V (13.5%)415.2 V106.87 V (22.27%)6733.1 WDrop/Amp High
6 AWG13.3 mm²65 A40.77 V (8.49%)439.2 V67.26 V (14.01%)4237.3 WDrop/Amp High
4 AWG21.15 mm²85 A25.64 V (5.34%)454.4 V42.29 V (8.81%)2664.6 WDrop/Amp High
3 AWG26.67 mm²100 A20.33 V (4.24%)459.7 V33.54 V (6.99%)2113.1 W~ ≤5%
2 AWG33.62 mm²115 A16.13 V (3.36%)463.9 V26.61 V (5.54%)1676.3 W~ ≤5%
1 AWG42.41 mm²130 A12.79 V (2.66%)467.2 V21.09 V (4.39%)1328.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A10.14 V (2.11%)469.9 V16.72 V (3.48%)1053.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A8.04 V (1.68%)472.0 V13.27 V (2.76%)835.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A6.38 V (1.33%)473.6 V10.52 V (2.19%)662.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A5.06 V (1.05%)474.9 V8.34 V (1.74%)525.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.28 V (0.89%)475.7 V7.06 V (1.47%)444.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.57 V (0.74%)476.4 V5.89 V (1.23%)370.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.06 V (0.64%)476.9 V5.05 V (1.05%)317.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.68 V (0.56%)477.3 V4.41 V (0.92%)278.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.14 V (0.45%)477.9 V3.53 V (0.74%)222.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.78 V (0.37%)478.2 V2.94 V (0.61%)185.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.43 V (0.3%)478.6 V2.35 V (0.49%)148.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.07 V (0.22%)478.9 V1.77 V (0.37%)111.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 800 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 800 feet one-way at 480V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 12.79V (2.66%) and delivers 467.2V at the load.

What size aluminum wire is required for 60 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 13.27V (2.76%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.