⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.59%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 3.31V (0.69%)
Voltage at Load End477.2 VLoss: 2.85 V (1108.9 W)
Power & Breaker (125%)187.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A146.65 V (30.55%)333.3 V241.91 V (50.4%)57152.2 WDrop/Amp High
12 AWG3.31 mm²20 A92.16 V (19.2%)387.8 V152.01 V (31.67%)35914.4 WDrop/Amp High
10 AWG5.26 mm²30 A57.99 V (12.08%)422.0 V95.66 V (19.93%)22600.1 WDrop/Amp High
8 AWG8.37 mm²50 A36.44 V (7.59%)443.6 V60.12 V (12.52%)14202.7 WDrop/Amp High
6 AWG13.3 mm²65 A22.94 V (4.78%)457.1 V37.83 V (7.88%)8938.1 WDrop/Amp High
4 AWG21.15 mm²85 A14.42 V (3.0%)465.6 V23.79 V (4.96%)5620.6 WDrop/Amp High
3 AWG26.67 mm²100 A11.44 V (2.38%)468.6 V18.87 V (3.93%)4457.3 WDrop/Amp High
2 AWG33.62 mm²115 A9.07 V (1.89%)470.9 V14.97 V (3.12%)3535.9 WDrop/Amp High
1 AWG42.41 mm²130 A7.19 V (1.5%)472.8 V11.86 V (2.47%)2803.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.7 V (1.19%)474.3 V9.41 V (1.96%)2222.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.52 V (0.94%)475.5 V7.46 V (1.55%)1763.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.59 V (0.75%)476.4 V5.92 V (1.23%)1398.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.85 V (0.59%)477.2 V4.69 V (0.98%)1108.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.41 V (0.5%)477.6 V3.97 V (0.83%)938.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.01 V (0.42%)478.0 V3.31 V (0.69%)782.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.72 V (0.36%)478.3 V2.84 V (0.59%)670.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.5 V (0.31%)478.5 V2.48 V (0.52%)586.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.2 V (0.25%)478.8 V1.99 V (0.41%)469.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.0 V (0.21%)479.0 V1.66 V (0.34%)391.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.8 V (0.17%)479.2 V1.32 V (0.28%)312.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.6 V (0.13%)479.4 V0.99 V (0.21%)234.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 120 feet one-way at 480V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 2.85V (0.59%) and delivers 477.2V at the load.

What size aluminum wire is required for 225 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 3.31V (0.69%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.