🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 80 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.4%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 2.21V (0.46%)
Voltage at Load End478.1 VLoss: 1.9 V (739.3 W)
Power & Breaker (125%)187.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 80 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A97.77 V (20.37%)382.2 V161.27 V (33.6%)38101.5 WDrop/Amp High
12 AWG3.31 mm²20 A61.44 V (12.8%)418.6 V101.34 V (21.11%)23942.9 WDrop/Amp High
10 AWG5.26 mm²30 A38.66 V (8.05%)441.3 V63.77 V (13.29%)15066.7 WDrop/Amp High
8 AWG8.37 mm²50 A24.3 V (5.06%)455.7 V40.08 V (8.35%)9468.5 WDrop/Amp High
6 AWG13.3 mm²65 A15.29 V (3.19%)464.7 V25.22 V (5.25%)5958.7 WDrop/Amp High
4 AWG21.15 mm²85 A9.62 V (2.0%)470.4 V15.86 V (3.3%)3747.1 WDrop/Amp High
3 AWG26.67 mm²100 A7.62 V (1.59%)472.4 V12.58 V (2.62%)2971.5 WDrop/Amp High
2 AWG33.62 mm²115 A6.05 V (1.26%)474.0 V9.98 V (2.08%)2357.3 WDrop/Amp High
1 AWG42.41 mm²130 A4.8 V (1.0%)475.2 V7.91 V (1.65%)1868.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.8 V (0.79%)476.2 V6.27 V (1.31%)1481.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.02 V (0.63%)477.0 V4.97 V (1.04%)1175.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.39 V (0.5%)477.6 V3.95 V (0.82%)932.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.9 V (0.4%)478.1 V3.13 V (0.65%)739.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.61 V (0.33%)478.4 V2.65 V (0.55%)625.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.34 V (0.28%)478.7 V2.21 V (0.46%)521.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.15 V (0.24%)478.9 V1.89 V (0.39%)447.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.0 V (0.21%)479.0 V1.65 V (0.34%)391.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.8 V (0.17%)479.2 V1.32 V (0.28%)312.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.67 V (0.14%)479.3 V1.1 V (0.23%)260.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.54 V (0.11%)479.5 V0.88 V (0.18%)208.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.4 V (0.08%)479.6 V0.66 V (0.14%)156.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 80 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 80 feet one-way at 480V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 1.9V (0.4%) and delivers 478.1V at the load.

What size aluminum wire is required for 225 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 2.21V (0.46%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.