⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 0.62%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 3.45V (0.72%)
Voltage at Load End477.0 VLoss: 2.96 V (1155.1 W)
Power & Breaker (125%)187.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A152.76 V (31.83%)327.2 V251.99 V (52.5%)59533.5 WDrop/Amp High
12 AWG3.31 mm²20 A96.0 V (20.0%)384.0 V158.35 V (32.99%)37410.8 WDrop/Amp High
10 AWG5.26 mm²30 A60.41 V (12.59%)419.6 V99.65 V (20.76%)23541.8 WDrop/Amp High
8 AWG8.37 mm²50 A37.96 V (7.91%)442.0 V62.62 V (13.05%)14794.5 WDrop/Amp High
6 AWG13.3 mm²65 A23.89 V (4.98%)456.1 V39.41 V (8.21%)9310.5 WDrop/Amp High
4 AWG21.15 mm²85 A15.02 V (3.13%)465.0 V24.78 V (5.16%)5854.8 WDrop/Amp High
3 AWG26.67 mm²100 A11.91 V (2.48%)468.1 V19.65 V (4.09%)4643.0 WDrop/Amp High
2 AWG33.62 mm²115 A9.45 V (1.97%)470.5 V15.59 V (3.25%)3683.2 WDrop/Amp High
1 AWG42.41 mm²130 A7.49 V (1.56%)472.5 V12.36 V (2.57%)2919.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.94 V (1.24%)474.1 V9.8 V (2.04%)2315.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.71 V (0.98%)475.3 V7.77 V (1.62%)1836.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.74 V (0.78%)476.3 V6.17 V (1.28%)1456.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.96 V (0.62%)477.0 V4.89 V (1.02%)1155.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.51 V (0.52%)477.5 V4.14 V (0.86%)977.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.09 V (0.44%)477.9 V3.45 V (0.72%)814.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.79 V (0.37%)478.2 V2.96 V (0.62%)698.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.57 V (0.33%)478.4 V2.59 V (0.54%)610.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.25 V (0.26%)478.7 V2.07 V (0.43%)488.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.05 V (0.22%)479.0 V1.72 V (0.36%)407.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.84 V (0.17%)479.2 V1.38 V (0.29%)325.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.63 V (0.13%)479.4 V1.03 V (0.22%)244.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 125 feet one-way at 480V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 2.96V (0.62%) and delivers 477.0V at the load.

What size aluminum wire is required for 225 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 3.45V (0.72%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.