🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.64V (3.19%)
Voltage at Load End233.8 VLoss: 6.18 V (1390.4 W)
Power & Breaker (125%)54.0 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1128.93 V (470.39%)0.0 V1862.21 V (775.92%)254009.8 WDrop/Amp High
12 AWG3.31 mm²20 A709.42 V (295.59%)0.0 V1170.21 V (487.59%)159619.4 WDrop/Amp High
10 AWG5.26 mm²30 A446.42 V (186.01%)0.0 V736.39 V (306.83%)100444.9 WDrop/Amp High
8 AWG8.37 mm²50 A280.55 V (116.89%)0.0 V462.77 V (192.82%)63123.1 WDrop/Amp High
6 AWG13.3 mm²65 A176.55 V (73.56%)63.4 V291.23 V (121.35%)39724.8 WDrop/Amp High
4 AWG21.15 mm²85 A111.03 V (46.26%)129.0 V183.14 V (76.31%)24980.6 WDrop/Amp High
3 AWG26.67 mm²100 A88.05 V (36.69%)152.0 V145.23 V (60.51%)19810.3 WDrop/Amp High
2 AWG33.62 mm²115 A69.84 V (29.1%)170.2 V115.21 V (48.0%)15715.1 WDrop/Amp High
1 AWG42.41 mm²130 A55.37 V (23.07%)184.6 V91.33 V (38.06%)12457.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A43.9 V (18.29%)196.1 V72.41 V (30.17%)9877.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A34.82 V (14.51%)205.2 V57.44 V (23.93%)7835.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.62 V (11.51%)212.4 V45.56 V (18.99%)6215.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.9 V (9.13%)218.1 V36.13 V (15.06%)4928.5 WDrop/Amp High
250 kcmil126.7 mm²255 A18.53 V (7.72%)221.5 V30.57 V (12.74%)4170.0 WDrop/Amp High
300 kcmil152.0 mm²285 A15.45 V (6.44%)224.6 V25.48 V (10.62%)3475.9 WDrop/Amp High
350 kcmil177.3 mm²310 A13.24 V (5.52%)226.8 V21.85 V (9.1%)2979.9 WDrop/Amp High
400 kcmil202.7 mm²335 A11.58 V (4.83%)228.4 V19.11 V (7.96%)2606.5 W~ ≤5%
500 kcmil253.4 mm²380 A9.27 V (3.86%)230.7 V15.29 V (6.37%)2085.0 W~ ≤5%
600 kcmil304.0 mm²420 A7.72 V (3.22%)232.3 V12.74 V (5.31%)1738.0 W~ ≤5%
750 kcmil380.0 mm²475 A6.18 V (2.57%)233.8 V10.19 V (4.25%)1390.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.63 V (1.93%)235.4 V7.64 V (3.19%)1042.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 800 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.18V (2.57%) and delivers 233.8V at the load.

What size aluminum wire is required for 225 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.64V (3.19%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.