🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.78%
Aluminum Wire (≤3% Drop)2 AWGDrop: 13.86V (2.89%)
Voltage at Load End466.6 VLoss: 13.35 V (578.3 W)
Power & Breaker (125%)20.78 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A135.79 V (28.29%)344.2 V223.99 V (46.66%)5879.9 WDrop/Amp High
12 AWG3.31 mm²20 A85.33 V (17.78%)394.7 V140.75 V (29.32%)3694.9 WDrop/Amp High
10 AWG5.26 mm²30 A53.7 V (11.19%)426.3 V88.57 V (18.45%)2325.1 WDrop/Amp High
8 AWG8.37 mm²50 A33.74 V (7.03%)446.3 V55.66 V (11.6%)1461.2 WDrop/Amp High
6 AWG13.3 mm²65 A21.24 V (4.42%)458.8 V35.03 V (7.3%)919.6 W~ ≤5%
4 AWG21.15 mm²85 A13.35 V (2.78%)466.6 V22.03 V (4.59%)578.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A10.59 V (2.21%)469.4 V17.47 V (3.64%)458.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A8.4 V (1.75%)471.6 V13.86 V (2.89%)363.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A6.66 V (1.39%)473.3 V10.99 V (2.29%)288.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A5.28 V (1.1%)474.7 V8.71 V (1.81%)228.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.19 V (0.87%)475.8 V6.91 V (1.44%)181.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.32 V (0.69%)476.7 V5.48 V (1.14%)143.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.63 V (0.55%)477.4 V4.35 V (0.91%)114.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.23 V (0.46%)477.8 V3.68 V (0.77%)96.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.86 V (0.39%)478.1 V3.07 V (0.64%)80.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.59 V (0.33%)478.4 V2.63 V (0.55%)69.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.39 V (0.29%)478.6 V2.3 V (0.48%)60.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.11 V (0.23%)478.9 V1.84 V (0.38%)48.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.93 V (0.19%)479.1 V1.53 V (0.32%)40.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.74 V (0.15%)479.3 V1.23 V (0.26%)32.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.56 V (0.12%)479.4 V0.92 V (0.19%)24.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 1000 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 13.35V (2.78%) and delivers 466.6V at the load.

What size aluminum wire is required for 25 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 13.86V (2.89%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.